  1. B

    Programmer problem

    Yes I agree! However, until very recently it has been working perfectly well for about four years.
  2. B

    Programmer problem

    The original installation had 2, but this was changed some time ago so now only 1.
  3. B

    Programmer problem

    Correct. Motorised Valve and programmer both new.
  4. B

    Programmer problem

    I removed the programmer and the CH still works using the FSU
  5. B

    Programmer problem

    We don’t have a room stat. Thanks everyone all the input by the way.
  6. B

    Programmer problem

    The valve only opens if I use the fused switch. It used to work fine with a programmer, stopped working, so I changed the motorised valve and timer but still no luck.
  7. B

    Programmer problem

    If I just use the fused switch the motorised valve opens and the system works.
  8. B

    Programmer problem

    Yes. It happened with the old programmer. So I thought the programmer was faulty so put a new one in. But still the same issue.
  9. B

    Programmer problem

    Nothing happens. If the fused switch is on the heating comes on even if the programmer is in the off position. Power also goes to the programmer.
  10. B

    Programmer problem

    Yes exactly! And the heating is working. I can operate the heating using the single switch.
  11. B

    Programmer problem

    I have a simple set up with a programmer opening a motorised valve/actuator to operate the central heating. Recently the heating stoped working. The valve still open scans closes correctly but I replaced the programmer - connections were the same as the old one (N L 3 4). I get the heating to...