  1. D

    draining a combi boiler

    Boiler will vent automatically via auto air vent at pump. Pump should move most air into system. I was refering to air at rads.
  2. D

    draining a combi boiler

    You have got it just about right Robbie. On refilling expect a bit of air to be vented.
  3. D

    Vokera linea 24 error 4

    I think you are wrong Tony this boiler does have a Water pressure switch. It is located on the hydraulic Manifold as described by Davie.
  4. D

    Vokera linea 24 error 4

    Indication are that the pressure switch is faulty. If your are qualified/competent to carry out tests as per the electrical faut finding guide you should be able to identify the offending component. £250 for the pair including labour is not far of the mark. Perhaps a second opinion could...
  5. D

    Vokera linea 28 domestic hot water problem

    From one old time spark to another, I had a similar fault with my linea 28. As the temperature approaches the preset, the gas valve should start to modulate down via info from thermistors. To replace the thermistors is relatively inexpensive and would be my first line of attack. There are 2 of...
  6. D

    Vokera Linea 28 - error 03?

    When you are on CH. the system water will expand and show this on the pressure gauge. Depending on the temperature setting the amount of expansion will vary, around 2 bar is acceptable. As the water cools the pressure in the system will drop. Can not identify a connection with this and the 03 fault.
  7. D

    Vokera Linea 28 - error 03?

    Hi Pete Had a similar problem with code 03 fault, indication was the fan motor was not up to producing the necessary flow rate or that the air proving switch was faulty. Fault was finally found to be deposits in the venturi tube,which is the connection on the flue that connects the flex tube...
  8. D

    gas boiler noise

    Sound as the boiler may be ketteling due to an internal flow restriction. Is the system water showing any sign of discoloration. I dont think a full cleansing ie Descale,complete flush and then inhibitor would go a miss.
  9. D

    gas boiler noise

    Hi Duggie Have you checked the system pump, the are known to make some strange noises.
  10. D

    Exel 80 SP. Poor DHW.

    Thanks for the quick response lads, Will try isolating heating valves as suggested gordon gas, was the part you replaced in the divert valve. Andsam, the plate heat exch. is attached to the back of the divert valve and would indicate the older model. Does the fittings your mentioned that are...
  11. D

    Exel 80 SP. Poor DHW.

    Appreciate any help with this boiler giving low temp DHW. Limited experience with combies. Have fitted service kit and flow thermistor. Boiler modulates down to to low flame and both main heat exchanger pipes are really hot. Heat not transferring to DHW outlet unless the flow is screwed down to...
  12. D

    Who are these corgi plumbers.

    A rather long winded description of how not to give a tinkers cuss Corgiman. Got it in one Meldrews mate, althouth the intention was not a row but to determine who is in a position to quantify competence. Some of the prema-donas that post on this forum are quick to condemn and question...
  13. D

    Who are these corgi plumbers.

    It is now the case that I can puchase all the kit I need to install central heating from my local B&Q Store.The mechanics of the install is mechano and could be carried out by anyone with a little common sense and a basic understanding of plumbing. Manufacturers litriture is quite explicate re...
  14. D

    High system pressure

    First thing that would be questioned is the present pressure in your expansion vessel. If the cold fill pressure is 1.8 bar then the vessel should be filled to a minimum of 1.8 bar. With 6 psi bag pressure and an operating pressure of 2.4 bar your press vessel is serving no purpose and the whole...
  15. D

    Hot water, but no heating on a combi boiler!?!?!

    What fault have you identified with CH switch.
  16. D

    [b]Boiler Firing-Up,Cutting-Out,Firing-Up etc =NO HOT WATER

    If the boiler was not installed by a recognised installer then I would advise you contact one and have the boiler properly commissioned. During the commission proceedure any plumbing faults would be corrected and more importantly the gas install/rating would be checked.
  17. D

    Vokera Mynute 12 - 48 Problem.

    Any ideas on the reason for this boiler not firing. Flue fan is running, Air pressure switch seems ok, pump is running and the pilot is established. The main gas will not fire. Appreciate any response.
  18. D

    Glow worm System 60 Boiler

    Thanks to all who responded for your help, especially croydoncorgi. Checked flow sensor as you suggested and it proved to be the culprit. Replaced sensor and boiler now operating normally. Thanks again.
  19. D

    Glow worm System 60 Boiler

    Having trouble with the boiler flow water temperature not going any higher than around 30c. When this temp is reached the boiler then modulates on - off around 30c with the temp control set at max. Any ideas please.