    Thermecon 60/80 oil boiler, Ecoflam Minor1, Delta VM1

    Hi roguetrader, the short answer is no. The longer answer is that (some) oil was getting through; I could “feel” it working with my fingers, and I tried removing the weight from inside the valve. Seems a distant memory already. Lovely and warm.
  2. N

    Thermecon 60/80 oil boiler, Ecoflam Minor1, Delta VM1

    It's warm in here. I picked up the Ecoflam Max1 from Wolseley this afternoon, £408 inc vat. It's quite a bit lighter that the old Minor. I was impressed to find it pre-primed and to see a little singeing on the burner tube suggesting a test. 1-pipe set-up out of the box, thankfully. It...
  3. N

    Thermecon 60/80 oil boiler, Ecoflam Minor1, Delta VM1

    Thanks everyone. I can only guess how frustrating it is for professionals to hear what a DIYer is up to. I appreciate your help. Burnerman - it's always the wrong time of year that the boiler goes wrong. If I could have got an engineer out in time I'd have gladly done so but NYE is even more...
  4. N

    Thermecon 60/80 oil boiler, Ecoflam Minor1, Delta VM1

    I should say that I am inclined to agree that the pump is at fault. There's plenty of oil spewing forth when the line to the nozzle holder is disconnected, but I have no pressure gauge to measure directly (although I did do a quick search on BES). Those magic discs do show signs of wear too...
  5. N

    Thermecon 60/80 oil boiler, Ecoflam Minor1, Delta VM1

    Thanks both, John, see the wires at the back of the nozzle holder, you can just make out the 2 yellow which feed to the control box, also 2 thin red wires in that sheath that you can also see in the box, 1 common with a yellow (terminal 8 ). Photocell goes to 11/12, ie 2 leftmost terminals...
  6. N

    Thermecon 60/80 oil boiler, Ecoflam Minor1, Delta VM1

    OK John, an update. (spoiler alert - no joy) Timings are about as above, and with the coil disconnected, I got 240v across the connector after about 8 seconds, so that looks ok. Emboldened by your sensible advice to have a go at the controller, I took it apart. What a little jewel of a device...
  7. N

    Thermecon 60/80 oil boiler, Ecoflam Minor1, Delta VM1

    Good plan John. My suspicion is that there's no flame at all for the photocell to see. I can hear (and feel) something at the solenoid, and as you say, it's hard to picture any oil getting to the nozzle otherwise. 8 seconds sounds about right, I might time it. The control box seemed a bit...
  8. N

    Thermecon 60/80 oil boiler, Ecoflam Minor1, Delta VM1

    Hi John, That was way quicker than I hoped. The photocell is spotless, I don't hear that sound of a flame that we all love. Control box ruthlessly German (it says here): LANDIS & GYR LOA22, if that means anything to you. Many thanks, Mike
  9. N

    Thermecon 60/80 oil boiler, Ecoflam Minor1, Delta VM1

    Hi folks, Please go easy on a curious/desperate amateur. I've been in this chilly house for 18 years with this set-up providing plenty of heat; the boiler instruction book says 1995. The ageing radiators were flushed about 5 years ago and work fine. I got a top-up of oil just before...