    How to set a bypass valve

    I bow to your superior knowledge in these things Johntheo5. My downstairs heating suffers from terrible TRV noise !. Upstairs far less. The new downstairs pipe runs are much shorter so flow rate will be higher ??. Can / should I try another setting on the pump and if so which. ( my...
  2. G

    How to set a bypass valve

    Grundfos operating instructions for the UPS3 attached. Section 6 6.2.1 Refers to the factory setting of Constant curve or Constant speed 1,2 or 3. 6.2.2 * Proportional pressure mode is not recommended in heating systems that include an ABV. BUT, I also found this on their website ...
  3. G

    How to set a bypass valve

    Grundfos UPS3 pump settings https://www.heatweb.co.uk/w/index.php?title=Grundfos_Pump_Settings#:~:text=The%20Grundfos%20pump%20has%203,LED%20and%204%20yellow%20LEDs.&text=When%20you%20switch%20on%20the,setting%20or%20the%20last%20setting.
  4. G

    How to set a bypass valve

    Grundfos recommend the constant pressure setting for the UPS3 pump on central heating systems fitted with ABVs. Ie fixed speed 1,2 or 3. The pump does have a proportional pressure setting but as they state, only to be used on a system with no ABV. An option I am considering and Johntheo5 could...
  5. G

    How to set a bypass valve

    Good evening Johntheo5, Update. Firstly I have found out why the pump was cutting out in anti cycle mode activation. Pump overrun was set at 5 minutes and anti cycle 6 minutes.I changed the pump overrun to 8 minutes and that solved that one. Boiler set to partial load 11 KW. I see that d.085...
  6. G

    How to set a bypass valve

    Thanks Johntheo5 Will do tomorrow and get back.
  7. G

    How to set a bypass valve

    Sorry, I should have added. When d.40 started rising over the 63 C set point, I quickly opened the TRV on bedroom 1 (largest radiator upstairs) and both flow and return temperature dropped and the boiler stabilised for quite some time modulating at 62 C. Flow and return did eventually rise to...
  8. G

    How to set a bypass valve

    d.40 rises to 67 - 68 C and d.41 is about 59 C. The rising of d.40 to 68 C starts the anti cycle. The boiler burner trips followed by the pump several minutes later. d. 41 drops to about 55 C, the pump restarts ( anti cycles looks to be four minutes) followed by the burner, d.40 rises to 68 C...
  9. G

    How to set a bypass valve

    Many thanks Johntheo5, I am very grateful for your help. I have attached a picture of the heating pipework. As you can see, the plumbers extended the 22 mm flow and return pipes so no more than three radiators could be on 15 mm pipes. Understandable I believe. My wondering in doing this, is...
  10. G

    How to set a bypass valve

    Hi Johntheo5 Update. I lowered the partial loading setting to 12KW. This dramatically slowed down the the initial heating up time from cold and seemed far more controlled. With the flow temperature still set at 63, it come up to temperature and modulated for some time. Great I thought. Then the...
  11. G

    How to set a bypass valve

    Hi SpecialK Rooms are not getting up to temperature.
  12. G

    How to set a bypass valve

    Hi Johntheo5 I,m beginning to think that this is a loading issue. Because I am in the middle of refurbishing the house I do not have all the rads fitted. So the current total loading is 10.59 KW. Split 5.87 KW downstairs and 4.72 KW upstairs. Boiler is 24 KW. All rads have TRV4s fitted. We...
  13. G

    How to set a bypass valve

    Worth me saying how I got to this situation. Updated old vented system to sealed system. Retained Valiant ecotech plus 424 boiler (24KW) and magnaclean filter. New Grundfos UPS3, Honeywell bypass, motorized valves for downstairs CH, upstairs CH and HW, Honeywell home wireless wall thermostats...
  14. G

    How to set a bypass valve

    The pump does seem to be quietThank you BlueLoo and Johntheo5 I am a real novice when it comes to central heating unfortunately so any advice gratefully received. The pump does seem to be quiet powerful to me as some of the TVRs (TRV4s) are noisy with water velocity. I believe from Grundfos...
  15. G

    How to set a bypass valve

    Hi Johntheo5 Honeywell straight connection which is set at 4. Boiler is firing up from cold and continues up to running temperature which is set at 62C flow. It seems happy with all TRVs open but temp starts rising beyond the 62 and in anti cycle mode once TRVs start closing. Temp then goes to...
  16. G

    How to set a bypass valve

    Its a UPS3 set on constant pressure 1.
  17. G

    How to set a bypass valve

    Hi Noddy997, New Grundfos UPS3
  18. G

    How to set a bypass valve

    Hi, can anyone tell me the minimum flow rate for a Valiant ecotech plus 424 boiler. I am trying to set my Honeywell bypass valve. (boiler keeps over heating and going into anti cycle mode). I think it could be lack of flow ?. Cheers Graham.
  19. G

    Grundfoss pump to powerful ?

    Boiler flow temperature set at 67 C. Return 55 C. I think I will have a go at balancing the system via the TRVs (Drayton TRV4s) using the Drayton balancing key. I have ordered some clip on thermostats to check across each rad as well.
  20. G

    Grundfoss pump to powerful ?

    I am wondering if radiant heat from the rads is causing the TRVs to react early ?. The issues are more where the TRVs are controlling vertical column steel radiators. The system has been bled several times and the pump is quiet. No F & E tank as the system is sealed / pressurised. Could it be a...