Search results

  1. B

    Worcester 24, 28CDI Nest Thermostat

    Well we have truly entered the twilight zone. Got home from work yesterday evening and my wife says the heating isn't coming on. Of course, like the previous evening the old stat is working. so I try turning it up and down, nothing. left it on a higher setting. Turned the nest up, still nothing...
  2. B

    Worcester 24, 28CDI Nest Thermostat

    Thanks, will give it a go when I get home this evening Hi, so module unplugged, Lr & Ls disconnected, nothing happens. Plug module in with Lr,Ls disconnected, nothing happens even with old stat above ambient temp. Tried Nest wires other way round in Ls,Rs and same as before. Old stat above...
  3. B

    Worcester 24, 28CDI Nest Thermostat

    So, with the old stat and nest under ambient temp, as soon as I disconnect the module, the heating fires up. I tried with the old stat set above ambient temp and nest below, pulled module and it fired up the heating. As for testing, black and red 23.7v (black is negative) nothing on green...
  4. B

    Worcester 24, 28CDI Nest Thermostat

    I took the link out at ST8, Ls and Lr when I put the Nest wires in. Otherwise everything is as it was.
  5. B

    Worcester 24, 28CDI Nest Thermostat

    If I set the nest to a lower temp than ambient, and set the old stat higher, the heating comes on. Oh, I didn't see it post so I replied again
  6. B

    Worcester 24, 28CDI Nest Thermostat

    And I connected 2 from nest "common" to ST8 LS and 3 from nest "call for heat" to St8 LR
  7. B

    Worcester 24, 28CDI Nest Thermostat

    Think its in the on position, if I set the nest to a lower temp than ambient, turn the existing stat up, the heating still comes on.
  8. B

    Worcester 24, 28CDI Nest Thermostat

    Hi and thanks. If I set the nest to a lower temp than ambient, turn the existing stat up, the heating still comes on.
  9. B

    Worcester 24, 28CDI Nest Thermostat

    Well that has worked to a certain extent, fuse isn't blowing. But, heating is not coming on. Should I be setting the installed room stat on the boiler to something specific? Or disconect it? It's in the "on" mode at the moment
  10. B

    Worcester 24, 28CDI Nest Thermostat

    Awesome, will give it a go. Thank you very much :-)
  11. B

    Worcester 24, 28CDI Nest Thermostat

    On the nest, terminal 2 and 3 to ST8 terminal 1 and 2 with the link removed. And the fuse that blew was on the pcb next to the mains wire in. 5x20 2A
  12. B

    Worcester 24, 28CDI Nest Thermostat

    It's old. 24 or 28CDI Worcester. connections in the pic I first posted, On the nest, terminal 2 and 3 to ST8 terminal 1 and 2 with the link removed
  13. B

    Worcester 24, 28CDI Nest Thermostat

    In the picture I posted, it shows a terminal block, ST13. On my PCB it is not there, only the solder points for the block.
  14. B

    Worcester 24, 28CDI Nest Thermostat

    Hi and thanks, connecting to ST8 blows the fuse on the circuit board. And yes, I used the correct terminals
  15. B

    Worcester 24, 28CDI Nest Thermostat

    Hi all, My first post so please be gentle. I have a Worcester 24 or 28CDI. Trying to connect a Nest Gen 3 Pro Thermostat. ST8 is mains so as I beleiev the Nest is 24v I would attach to St13, No11 in the pic. But my boiler only has PCB solder point and no connecter as per the picture...