Search results

  1. T

    Water hammer from unvented cylinder

    Got held up with other stuff. I will report back on here when I've made some progress. Keen we all learn from this!
  2. T

    Water hammer from unvented cylinder

    Yeah just dishwater, hosepipe and kitchen cold off the mains. The rest of the house goes through the balanced cold.
  3. T

    Water hammer from unvented cylinder

    It depends on the time of day. I think if there's positive pressure from the HW connection it's not as loud
  4. T

    Water hammer from unvented cylinder

    If it is that's crazy it's been replaced and both had the same problem!
  5. T

    Water hammer from unvented cylinder

    Yeah job for the weekend to have a play.
  6. T

    Water hammer from unvented cylinder

    It’s a new ICG!
  7. T

    Water hammer from unvented cylinder

    Caleffi were confident it’s not the NRV. But the more I listen the more I think it’s the ICG I don’t have the old one as I put it in the bin!
  8. T

    Water hammer from unvented cylinder

    Not since I put the PRV in. More like 4.5 during a spike now.
  9. T

    Water hammer from unvented cylinder

    Hi, I’ve done that before. Near the ICG it’s never spiked more than 5.
  10. T

    Water hammer from unvented cylinder

    The house had one arrestor T’d off the water meter. I added a second one before the ICG. That pressure gauge was on the second hammer arrestor. I tried opening the PRV yesterday. It just made the noise louder. That’s why it’s showing slightly more than 3 bar
  11. T

    Water hammer from unvented cylinder

    I was having a little play tonight. I connected a gauge to the mini expansion vessel valve just to see. This sits before the ICG
  12. T

    Water hammer from unvented cylinder

    Sorry I keep thinking I answered that and I don’t haha. Sorry! It’s 18L
  13. T

    Water hammer from unvented cylinder

    Yeap going to get some plastic piping probs at weekend and see. I did actually ring Caleffi UK yesterday - they were so helpful! The guy spent a good 30mins talking to me about the issue. He also thought the hammer was weird.
  14. T

    Water hammer from unvented cylinder

    Random thought tonight. Could a pipe bend too close to the balanced cold port cause issues?
  15. T

    Water hammer from unvented cylinder

    I'll give it another go!!
  16. T

    Water hammer from unvented cylinder

    Yeah tried that - it's hard to do because the shock is so strong you can hear/feel it on the inlet pipe, balanced cold, cylinder feed and even the EV leg!
  17. T

    Water hammer from unvented cylinder

    Sorry what I meant was if I open and close the hot water tap - you're still getting flow from through ICG but rather than going down the balanced cold connection it's going into the cylinder. It doesn't hammer when I do this. I'm confused though because someone said there's no NRV between...
  18. T

    Water hammer from unvented cylinder

    So this mixer is feeding all the hot taps in the house? Got me wondering now - as I've never checked this! Picture might be a small wait as I need to remove the bath panel which is sealed in!
  19. T

    Water hammer from unvented cylinder

    Sorry I probably missed this point there is a mini shock arrestor before the PRV, but I think thats the one you were suggesting making a bigger volume? That's what I'm thinking if during a heating event there is pressure build up and this is just pushing the NRV enough so it doesn't hammer...
  20. T

    Water hammer from unvented cylinder

    Wait so it's not just hot directly from the HW cylinder? I actually thought that mixer was something to do with the shower as it was under the bath! :)