  1. V

    Warmflow kc70hee combination oil boiler hot water issues

    Sorted thank you warmflow technical. Very good services
  2. V

    Warmflow kc70hee combination oil boiler hot water issues

    Hi I have a warmflow kc70hee combination oil boiler, the eco model with the single pump. Hot water mode dont turn off unless i turn front panel switch off, turning the hot water stat at rear of panel, i can hear it click but burner still goes. Turn eco on and all goes off and burner stops...
  3. V

    Warmflow oil combi boiler issue

    Sorted Was indeed the limit stat Cheers for the help
  4. V

    Warmflow oil combi boiler issue

    Yes I am a mechanical engineer I am doing process of elimination now
  5. V

    Warmflow oil combi boiler issue

    Changed all stats, got a spare boiler panel here you see And tried new p c b No different
  6. V

    Warmflow oil combi boiler issue

    So Gotta kc70hee warmflow combi oil boiler and was fine. Now the burner is not working and light in panel, burner light. So i changed the burner to a KNOWN working one off my sons boiler and still the same, swapped my burner to his boiler and is fine, so i think boiler is the issue. It has...
  7. V

    Heatslave 20/25 diverter valve problem.

    Hi all Gotta worcester heatslave 20/25 with a honeywell Vc4613 diversion valve. Lever up cartridge type Not too sure what's up but heating only come on when I turn up hot. water Port a on valve goes to heatslave hot water tank and. Port B goes to heating circuit. AB from the boiler. Seems...
  8. V

    Warmflow kc70hee oil boiler (releases pressure) (Ed.)

    Sorted .hose had collapsed internally. Appreciate your help
  9. V

    Warmflow kc70hee oil boiler (releases pressure) (Ed.)

    Thanks I will try later with my tyre gauge
  10. V

    Worcester heatslave oil boiler combi thermostat cut out

    Changed the diverter valve AGAIN and now still.the same !! And Changed heat exchanger ,all pipes are clear. Odd that I have same boiler in my shed that i use for just hit water and that is fine when i change all components over so might do a swap in the summer and see .
  11. V

    Worcester heatslave oil boiler combi thermostat cut out

    i have put another panel and thermostats on and will check it later.
  12. V

    Worcester heatslave oil boiler combi thermostat cut out

    So It worked fine for a while All controls working as they shoukd and hot water and central heating fine , then I turned heating off last night and then checked this morning reset tripped again
  13. V

    Worcester heatslave oil boiler combi thermostat cut out

    I will check. In morning Really appreciate all your help. Cheers
  14. V

    Worcester heatslave oil boiler combi thermostat cut out

    So Heating stat turn on and off ok no problem and turns off burner fine. Reset stat changed and exactly the same!! What next the water stat? But that seems fine Very odd
  15. V

    Worcester heatslave oil boiler combi thermostat cut out

    The heating control you mean mate ?
  16. V

    Worcester heatslave oil boiler combi thermostat cut out

    Well Changed heat exchanger tonight just in case and nee diverter valve, still same . Happens if just hot water is on or heating on. If heating on the rads get hot no problem then the reset kicks in so think.pumps running ok . Have had these boilers 15 years and built up a lot of spares so I...
  17. V

    Worcester heatslave oil boiler combi thermostat cut out

    I will look at those later thanks. The manual says to put the reset stat then limit stat then control stat in same pocket.on boiler. But on mine the control stat is on a separate pocket to the right above burner,still with a split pin in place