  1. Cameron_s92

    Garage lights trip RCD

    Here is the house CU, I believe that is a TN-S. This is before I started, the spare 32A MCB on the non RCD side is now on the RCD side and is being used for the garage
  2. Cameron_s92

    Garage lights trip RCD

    Yeah, rechecked the photos and I think i have followed the wrong neutral tail from the RCD so its on the wrong bar as you all pointed out. The other side of the main CU only has a 2 pole switch, and no RCD. If I moved the garage to that side, is there anything extra i would have to do to...
  3. Cameron_s92

    Garage lights trip RCD

    That's good to know, the EV is a long term plan, but didn't want to spend twice in 5 years.
  4. Cameron_s92

    Garage lights trip RCD

    Looking for a bit of guidance, we recently installed a garage consumer unit to replace the "twin and earth running up the driveway" job the previous owner left. We used 16mm SWA to future proof for EV charging. The T&E cable was running off a socket in the hallway and powering 3 LED battens and...