  1. J

    UFH running too hot

    Setting 1 the loop flow rates dropped slightly Setting 2 maintained the loop flow rates However the minimum temperature was 40c. I changed the blender and it started to control the temperature of the water. Changed the pump setting to the original and the flow rates dropped. Set it on...
  2. J

    UFH running too hot

    Despite saying I wouldn't do any further work until Monday, From the responses receive I did the following. Setting the blender to minimum I could hear the blender doing its work. Set midway the flow rates on the loops were correct. Set to minimum they dropped. With the blender set midway when...
  3. J

    UFH running too hot

    Despite saying I wouldn't do any further work until Monday, curiosity got the better of me. From the responses received I did the following. Setting the blender to minimum I could hear the blender doing its work. Set midway the flow rates on the loops were correct. Set to minimum they dropped...
  4. J

    UFH running too hot

    Thanks everyone for your suggestions. Lots for ne to try, plus a replacement blender valve has arrived. She who must be obeyed has decreed no more UFH work until Monday. I'll provide an update on progress next week
  5. J

    UFH running too hot

    The loops are 16mm
  6. J

    UFH running too hot

    Thanks Johntheo5, I'm out at the moment so I'll check when I get back later today. I'll put the radiators on as suggested and see what the UFH temperatures are like then. I don't understand why the blender is letting the water temperature get so high. It appears to be passing all the heat from...
  7. J

    UFH running too hot

    I've got thermometers on the flow and return of the manifold. Also got a hand held thermometer. The temperature of the loops is the same as the flow from the boiler 48c no matter what I set the blender to. The return pipe is getting warm, Wunda say the 22mm feed from the boiier should be 15mm...
  8. J

    UFH running too hot

    Thank you for your reply. The boiler is a Bosch Worcester CDi I'm not sure what the minimum output is, where would I find that? As far as I am aware there is no air in the system. I have run water through the loops until I no longer had air bubbles and there is no air coming out of the bleed...
  9. J

    UFH running too hot

    I am commissioning my Wunda UFH. All the flow rates have been set up as per the design. No matter what I set the blender to the flow temperature rises to 50c and drops to 30c as the boiler cycles. In addition if I set the blender to minimum the flow rates on each circuit drop to below 1 L/m from...