    Worcester Danesmoor 20/25 Intermittent lock out

    Mr Therm the pump is brand new complete with oil solenoid so I dont suspect sticking or faulty valve. It is the length of time after fan and ignition have started, it comes right at the end of the sequence just before lock out time. The previous solenoid /pump fired in a shorter time frame.
  2. F

    Worcester Danesmoor 20/25 Intermittent lock out

    Thanks fo rthe replies. The boiler was working fine before the motor and oil pump replaced, its not a "burning issue" nor CO, its a delayed oil solenoid opening time, I will replace the photocell and report back......having said that, the photocell wont see the flame because the burner is not...
  3. F

    Worcester Danesmoor 20/25 Intermittent lock out

    So I return..... the boiler has worked fine snce last episode in June //www.diynot.com/forums/plumbing/worcester-danesmore-rs-20-25-lock-out.405591/ Now after replacing Satronic control unit, ignition pack, pump and motor(yes I know cheaper to replace burner etc etc...). The boiler is...
  4. F

    Worcester Danesmore RS 20/25 LOCK OUT

    Yes the plastic drive coupling..... 98p ....now running fine.... in the words of Mutley the Dog "Rassen frassen plastic coupling !!"
  5. F

    Worcester Danesmore RS 20/25 LOCK OUT

    Internal lugs on plastic Bentone drive coupling stripped on motor shaft, so will fire up short amount of time due to friction in drive coupling, but as it warms up the coupling spins on oil pump shaft and stops oil delivery.
  6. F

    Worcester Danesmore RS 20/25 LOCK OUT

    Burnerman Thanks fo the pointers will look tomorrow morning
  7. F

    Worcester Danesmore RS 20/25 LOCK OUT

    Boilerman2 thanks for the vote of confidence, I do like your words of encouragement. With the cost of replacement parts being small and readily available for this unit I don't mind spending out for replacement parts, what I do mind is paying for a service technician to do exactly the same as I...
  8. F

    Worcester Danesmore RS 20/25 LOCK OUT

    ooops missed Awowen post, ...... boiler locked out again. I suspect plunger in Danfoss oil pump. or control box or both. No click from solenoid before I took plunger out now clicks and allows oil flow, however with boiler now locked out and me too tired. Will check tomorrow Thanks for the help...
  9. F

    Worcester Danesmore RS 20/25 LOCK OUT

    coil energises, removed solenoid plunger, is it meant to move ? tapped it and re built. Now on start up solenoid clicks and boiler fires. Still running after 1 hour. May need to change pump plunger valve assembly
  10. F

    Worcester Danesmore RS 20/25 LOCK OUT

    Thank you will look at the coil will check a voltage is being sent to coil with multimeter
  11. F

    Worcester Danesmore RS 20/25 LOCK OUT

    Good Morning All I have returned from working away to a none working boiler, the wife was highly delighted ! That and the World Cup on every channel !! Cleaned tank master filter, pump filter, and nozzle gauze filter. Tank has fuel, was firing after resetting lock out intermitently for 4...
  12. F