    RCD trips too slowly - why ?

    Hi, I have a Mem 2000AD consumer unit that is fitted with a 80A 30ma 30ms response time RCD. Its a A80HE. I have recently added a new circuit for a Hot Tub and on testing this the sparky found that it took 50ms to trip and said my RCD was faulty and would have to be replaced. He tested on...
  2. M

    Moving socket

    I'm installing furniture which as luck would have it - runs right down the middle of a double socket. Whats the easiest way of moving it a socket width to the right without causing a real mess? Thanks... Maurice
  3. M

    Wiring an isolator switch with 3 Core SWA

    I have a 4 pole 32A Rotary Isolator switch which I am planning to use to Isolate the supply to a Hot Tub. The supply is fed from a 3 Core 6mm2 SWA cable. The Isolator switch is obviously designed to switch 3 phase and Neutral and has two other earth connection points. My question are -...
  4. M

    Which CU?

    Hi, It's been recommended as I am supplying a Hot Tub in the garden and it needs to be on its own circuit. The recommendation is to enable me to future proof the supply somewhat by having a mini CU in the Garden enabling me to run further supplies in the future for lights / sockets etc...
  5. M

    Any regulations on distance for clips / cleats of SWA cable

    Hi, I'm installing 6mm2 SWA cable on the outside wall and across the loft. Are there any regulations relating to the distances between cleats either inside the loft or on the outside wall? Also any other no no's that I need to be aware of? I intended running the cable across the loft by...
  6. M

    Which CU?

    Hi, I have been recommeded a weatherproof CU MK5704 from TLC. I intend running 10mm2 SWA to the unit. I have read on the TLC site that it has 20mm knockouts and it looks plastic in its construction. 1. Will it being plastic affect my ability to terminate with a normal gland ? 2. The...
  7. M

    Why would I not use the armour in SWA as earth ?

    Hi, I'm involved in using some SWA cable over a longish run. As its quite expensive I think I'll be utilising the armour as the earth (as I know you have to earth it anyway). As a result I only need to puchase two core cable and it got me thinking - why would I ever puchase 3 core cable in...
  8. M

    When to use SWA and when not to use it?

    Hi, I have a need to install a 32A supply to the garden for Hot Tub. It a fairly long run of about 40m or so involving leaving the CU going up an external wall, across the loft, down an external wall to a weatherproof Mini CU. From the Mini CU I would then like to run to an Isolator...
  9. M

    Type of supply

    Hi, Whats a easy way of working out what sort of supply you have? Can I just ring the supplier ot the Local Authority? TT? TN-S or PME ? Thanks... Maurice
  10. M

    Hot tub installation questions

    Hi, I am thinking about installing a hot tub in the garden and I have a few questions. The hot tub in question apparently requires a 32A RCD. It has a 5.5kw heater and a number of other items / pumps which I am sure contribute to the majority of the 32A load - but i suspect it does not...