    Vaillant EcoTec Exclusive 838 13 rads

    absolutely, great idea - thanks everyone for your expert help
  2. D

    Vaillant EcoTec Exclusive 838 13 rads

    I am a Consultant surgeon and I bought the house from a property developer who did the heating installation - I'm no longer in contact with him. He asked me what boiler I wanted and I had heard vaillant were decent so I went for one which was for bigger houses and had a good flow. The one I...
  3. D

    Vaillant EcoTec Exclusive 838 13 rads

    The control was not on analogue so I have changed this as well as the setback to 17 as dangermouse suggested. Can you explain what the setback setting actually does? Also now it is on setback what about the other settings and what about the flow rates I posted recently are they ok? Thanks
  4. D

    Vaillant EcoTec Exclusive 838 13 rads

    Regarding flow and return Boiler started from overun 43 flow and return it went up incrementally ( 67/49 68/50 etc) with 70 degree flow and 52 return. This went up to max 70 flow 59 return and the boiler ran for 30 mins before overun at 70 flow 59 return. This is the best peformance...
  5. D

    Vaillant EcoTec Exclusive 838 13 rads

    the rads and boiler are all new, the house has had no other system for compsrison
  6. D

    Vaillant EcoTec Exclusive 838 13 rads

    Tony when I put it on 19 or 22 it took ages to get heat to the rads and the overun was coming on about the same and I could not get the temp to 21 degrees evben after 5 hours. On 30KW I can get to 21 degrees, in fact 30 seems better than 27. I have no explantion for it and i understand your...
  7. D

    Vaillant EcoTec Exclusive 838 13 rads

    they are cavity walls not insulated - because I want to avoid condensation that a mate got in a similar house when he had cavity wall insultaion put in. I don' t think I have too many rads, just one in each room and 2 in the kitchen and a towel rail in the bathroom. Also the boiler at 30KW...
  8. D

    Vaillant EcoTec Exclusive 838 13 rads

    the boiler control is via the Vaillant VRT360F
  9. D

    Vaillant EcoTec Exclusive 838 13 rads

    Could this be a balance problem causing the quick overun? I have tried a few different balance settings and it does not seem to make much difference. They all have thermostatic valves on and all the rads heat up ok though except one which seems to take a bit longer and the lockshield is max...
  10. D

    Vaillant EcoTec Exclusive 838 13 rads

    I have currently got the system on 30KW and bypass to max 350mb and pump on 100%, water overun at 5 mins and this seems to be not bad. 19KW as mentioned before was hopeless. However it seems to still go onto overun quite a lot. For example I put it on this morning ro raise the temp from 17.5...
  11. D

    Vaillant EcoTec Exclusive 838 13 rads

    The rad sizes and room sizes are as follows. The house is detatched 1930s Living room (5.18m x 5.18m x 2.59m) 175x52 double Dining room (4.57 x 3.65 x 2.59m) 175x52 double Kitchen (6.40 x 5.48 x 2.59m) 145 x 52 and 93x52 both doubles Hall (3.65 x 3.65 x2.59m) 154 x52 double WC...
  12. D

    Vaillant EcoTec Exclusive 838 13 rads

    Also, I've put the pump back to 100% as performance seems poor on the auto setting. I don't understand this as this is supposed to adjust automatically to the system. Any idea why this would be the case and should I try with the pump at a different % speed or will that stop it working at 100%...
  13. D

    Vaillant EcoTec Exclusive 838 13 rads

    I changed it to 19KW and it was hopeless - I've put it back to 30. Tony - the bypass is a screw with adjustability from 170mb to 350, the default is 250 which is what it is on now. Regarding the overun - some conflicting views here? The pump overun is currently on the default of 5mins...
  14. D

    Vaillant EcoTec Exclusive 838 13 rads

    I forgot to add that they are all 52cm high Myson double convectors on all but the 2 singles
  15. D

    Vaillant EcoTec Exclusive 838 13 rads

    Rad sizes are All sizes in cm 175 double 154 double 114 double 104 double 83 double 83 double 154 double 175 double 175 double 93 double 145 double 80 single 52 single thanks
  16. D

    Vaillant EcoTec Exclusive 838 13 rads

    Tony Thanks for the message. The reason that I have not changed it yet is because the previous response (not from you) just suggested an approximation KW based on the number of rads. The person replying did not ask about the rad size etc so the calculation might have been flawed. I have 13...
  17. D

    Vaillant EcoTec Exclusive 838 13 rads

    Many thanks to all who replied to my previous post on wed 4th Nov, much appreciated. I have a couple of other questions that I would appreciate comments on. It was mentioned from my last message that with 13 rads I should put the partial heat load to 19kw However even on the default of...
  18. D

    Vailant EcoTec Exclsive 838

    Hi I would appreciate any advice with questions below Vaillant EcoTec Exclusive 838 13 rads on system What is the most efficient burner anti cycle time with target feed of 70 degrees. The current default is 20mins. Also would you expect the default pump target value (Auto) to be...
  19. D

    Noise diagnosis?

    If I set the valve higher I get less noise but it takes much longer to get any heat in the system which seems very inefficient, I was wondering what would happen if I closed the valve off completely but I'm a bit apprehensive I might damage the system.
  20. D

    Noise diagnosis?

    Yes I think that is the valve you mentioned, it is a big brass valve with a plastic screw top with a scale marked in bar. The lowest setting is 0.5 and the closer the reference mark is to this the more noise I get. To be honest I'm not sure what this valve actually does. Thanks very much for...