Hiya
I've tried looking for other answers but nothing seems to answer it so here it goes.
My oven circuit is run in a 6mm to a twin socket that is supplying a 16amp oven and a 16amp microwave.
They are fed by a 32amp b type MCB.
The oven and microwave have a 13amp plug top on both.
Siemens came to repair the oven and stated......"wired in wrong, both need a 16amp power supply but were both wired in
with 13amp fuse plugs"
I understand the 13amp plug problem but the circuit itself is fine isn't it?
If so, can I just swap the the twin socket for 2x 20amp double pole switches?
Thank you in advance