If the UK leaves the EU, will the nominal voltage be changed back to 240v?

If the UK leaves the EU, do you think the nominal voltage will be increased from 230v to 240v?


  • Total voters
    25
Whatever, these discussions about detail are a bit irrelevant. Not only does the 230V 'nominal' electricity supply voltage in the UK not correspond to the 'expected'/'intended'/'observed' voltage, but nor does it correspond to the minimum, maximum, any sort of average (mean, median, mode or whatever) or any other summary statistic of the voltages which are actually supplied.
Indeed.

That is why it is called nominal, and not average.


Let's face it, it is surely the range of permitted voltages which actually matters.
It is.

But you seem to have a problem with a permitted voltage range being 207-253 when you won't find the supply ranging between those limits in any one location.


Would it make any difference if, rather than 230V ±10%, the 'target' figure was stated as 240V -10%/+5.5%? Both represent (approximately) 216V - 253V, and any voltage within that range would be acceptable
I always thought that 230 - 10% was 207.


so what is the significance in one having a 'nominal' value of 230V and the other a nominal value of 240V?
So what is the problem with a supply varying between 226V and 253V when the allowed range is 207-253?
 
Sponsored Links
That is only sometimes correct. In any case, you are agreeing that in such cases the nominal hfe is identical to the minimum.
Indeed - but the nominal hfe (if called 'nominal', rather than 'minimum') is, in the 'graded components' situation, nevertheless related to the average hfe of components with that 'nominal' value (the average being approximately the midpoint of values for that 'grade'). I'm actually not convinced that many manufacturers would call the minimum value the 'nominal' one.

Kind Regards, John
 
Yes, but as I keep saying, this whole 'untidiness' seems to exist because of the apparent obsession with declaring the range of voltages (whether permitted supply voltages or the working voltages of equipment) as "arbitrary nominal ± tolerances", rather than simply declaring the range - which is what actually matters.
This whole argument seems to exist because of the apparent obsession in some people with declaring the range of voltages as a simple range rather than "arbitrary nominal ± tolerances" - as if it actually matters.
 
The nominal weight of a 1 kg bag of sugar is 1 kg. The actual weight is subject to a tolerance that is both numerically and statistically asymmetric. Yes, the tolerance is a smaller value that 10%, but the principle is not altered by that.
Yes - but, by legislation (if e-marked), the declared 'nominal' weight is required to have a specified relationship to the average weight of actual bags of sugar.

The declared 'nominal' electricity supply voltage has, and is not required to have, any relationship to the average of actual supplied voltages. The fact that the 'nominal' voltage changed overnight without any change in supplied voltages is witness to that.

Kind Regards, John
 
Sponsored Links
This whole argument seems to exist because of the apparent obsession in some people with declaring the range of voltages as a simple range rather than "arbitrary nominal ± tolerances" - as if it actually matters.
It matters in the sense that the way in which is is done implies that 'nominal voltages' (without the tolerances, which turns them into a range) actually 'mean something' - which they don't (unless/until we eventually harmonise the actual supply voltages to correspond roughly with the arbitrary 'nominal' ones).

Kind Regards, John
 
It matters in the sense that the way in which is is done implies that 'nominal voltages' (without the tolerances, which turns them into a range) actually 'mean something' - which they don't (unless/until we eventually harmonise the actual supply voltages to correspond roughly with the arbitrary 'nominal' ones).
That's not an implication.

It is a faulty inference drawn by you and Winston.
 
The fact that the nominal value of 230V is harmonised throughout Europe and some other countries.[/QUOTE]As an arbitrary figure with which to associate ± tolerances so as to define the permitted range, yes, but why such a convoluted way of defining a permitted range? As PBC has said, one could have a 'nominal' voltage of 600V with 'tolerances' of -64%/-58% - and the 230V and 240V don't really have much more useful meaning than that 600V.

As I keep saying, the harmonisation makes sense if, and only if, it is part of a plan to move the actual average supply voltages in all countries close to 230V

Kind Regards, John
 
But you seem to have a problem with a permitted voltage range being 207-253 when you won't find the supply ranging between those limits in any one location.
Not at all - what makes you think that?
Would it make any difference if, rather than 230V ±10%, the 'target' figure was stated as 240V -10%/+5.5%? Both represent (approximately) 216V - 253V, and any voltage within that range would be acceptable
I always thought that 230 - 10% was 207.
Whoops - my arithmetic went a bit awry there. However, I'm sure you understand my point, and I will correct the original post.
so what is the significance in one having a 'nominal' value of 230V and the other a nominal value of 240V?
So what is the problem with a supply varying between 226V and 253V when the allowed range is 207-253?
[I presume you mean 216V] No problem, per se. Detlef is concerned that suppliers might take advantage of the additional ~9V wiggle room at the bottom and allow some supplies to fall to a level at which current equipment (designed to work above 216.2V) might not function satisfactorily.

Kind Regards, John
 
That is only sometimes correct. In any case, you are agreeing that in such cases the nominal hfe is identical to the minimum.
Indeed - but the nominal hfe (if called 'nominal', rather than 'minimum') is, in the 'graded components' situation, nevertheless related to the average hfe of components with that 'nominal' value (the average being approximately the midpoint of values for that 'grade'). I'm actually not convinced that many manufacturers would call the minimum value the 'nominal' one.

Kind Regards, John
IME, they all do.
 
The nominal weight of a 1 kg bag of sugar is 1 kg. The actual weight is subject to a tolerance that is both numerically and statistically asymmetric. Yes, the tolerance is a smaller value that 10%, but the principle is not altered by that.
Yes - but, by legislation (if e-marked), the declared 'nominal' weight is required to have a specified relationship to the average weight of actual bags of sugar.
Yes, that's what I said.
 
The declared 'nominal' electricity supply voltage has, and is not required to have, any relationship to the average of actual supplied voltages. The fact that the 'nominal' voltage changed overnight without any change in supplied voltages is witness to that.
No, that witnesses to the fact that the UK was successful in arguing that the tolerances around the nominal value would encompass the actual values of our supply, so there was no need for it to change.
 
JohnW2 said:
Yes - but, by legislation (if e-marked), the declared 'nominal' weight is required to have a specified relationship to the average weight of actual bags of sugar.
Yes, that's what I said.
Yes, but, as I went on to say, in contrast, the declared 'nominal' electricity supply voltage has, and is not required to have, any relationship whatsoever to the average of actual supplied voltages.

Kind Regards, John
 
JohnW2 said:
Yes - but, by legislation (if e-marked), the declared 'nominal' weight is required to have a specified relationship to the average weight of actual bags of sugar.
Yes, that's what I said.
Yes, but, as I went on to say, in contrast, the declared 'nominal' electricity supply voltage has, and is not required to have, any relationship whatsoever to the average of actual supplied voltages.

Kind Regards, John
I would have thought that the requirement for 95% of the 10-minute average values during a one-week period to remain within the specified tolerance is pretty fair evidence of a relationship.
 
But you seem to have a problem with a permitted voltage range being 207-253 when you won't find the supply ranging between those limits in any one location.
Perhaps not at the moment. But if the DNO's are, in effect, given permission to operate to the lower limit by the new standard, don't you think it's likely they may well make use of that in the future? Imagine increasing demand at the end of a long rural stretch of 240/415/480V (oops, make that 230/400/460V) distribution. If they can get away with allowing the voltage at the last house on the run dropping to 207V instead of having to maintain it at 216V minimum, don't you think they may well do so? They may well even adjust the transformer taps to deliver over 250V at no load in order to satisfy the 207V minimum at full load at the distant end. That means that the delvered voltage to that last house could well vary between over 250V during times of negligible load to 207V at peak demand.
 
No, that witnesses to the fact that the UK was successful in arguing that the tolerances around the nominal value would encompass the actual values of our supply, so there was no need for it to change.
If there was no need for the actual parameters of the U.K. supply to change, then why was there any need to change the parameters on paper?
 

DIYnot Local

Staff member

If you need to find a tradesperson to get your job done, please try our local search below, or if you are doing it yourself you can find suppliers local to you.

Select the supplier or trade you require, enter your location to begin your search.


Are you a trade or supplier? You can create your listing free at DIYnot Local

 
Sponsored Links
Back
Top