Recent content by kumbi

  1. K

    Can I run 4mm cable from a 6mm Control unit to my Hob.

    :D Thanks AGAIN Breezer, I think i will go back to fitting the kitchen now. GOD bless you... Kumbi :D
  2. K

    Can I run 4mm cable from a 6mm Control unit to my Hob.

    Breezer!!!!! thanks to you, you have saved myself and my kids lifes. The full story is I have a Hob and seperate oven: Setup: Hob: max 6 kw Total Apms 26.1 Oven:max 5.1 kw Total Apms 22. I bought the Oven refurbished(b-stock full warranty) and it came with a 1.5mm cable with a...
  3. K

    Can I run 4mm cable from a 6mm Control unit to my Hob.

    Thanks again Breezer!, :D
  4. K

    Can I run 4mm cable from a 6mm Control unit to my Hob.

    Just when I thought it was over another challenge appears, help please! I have 6mm cable running from my consumer unit, using a 30amp fuse to my control unit in the kitchen( was there Before). My new hob appliance uses 6.2kw. My existing 6mm cable will not fit, Manufacturer say's if you...
  5. K

    Can I run 4mm cable from a 6mm Control unit to my Hob.

    Just when I thought it was over another challenge appears, help please! I have 6mm cable running from my consumer unit (30amp Fused) to my large on/off double pole control unit in the kitchen. I have a 6mm spur from the control unit( existing setup). My new hob appliance uses 6.2kw. My...
  6. K

    extending a mains cable

    Thanks Breezer I ended up using junction boxes as you advised, I have seen the expert advice you have given in other subjects, thank you i'ts good to know there is some out there who does know what he is doing... have a good day. regards kumbi :D
  7. K

    ring circuit

    I want to move a socket (ring circuit) further away buy extending the two cables using 2 x(One for each Cable) 3amp Terminal Block connectors, that will be set inside a wall with the cables. I will skim over and then tile over. Is this recommended. Please help. Regards Kumbi
  8. K

    extending a mains cable

    Thank you breezer for the reply, I will sleep better at night now. One more question please, the same question as before but this time using 2 x 30amp Terminal Block connectors to extend the two 2.5mm cables. The Terminal blocks and the cables will be set inside a wall that i will skim over...
  9. K

    extending a mains cable

    I have a ring circuit at home and I wish to move the current socket to a further location. can I extend the two 2.5mm cables that are in the current socket, using a 30Amp Junction box? Is it good practice to extend 2.5mm cables and above using junction boxes. thanks kumbi