System was working up to when I drained it and then found I could not refill via the expansion tank/cold feed.
I can get a flexible pipe cleaning snake right up to the entry into the boiler, but it is a right angle bend so cannot put any pressure on the actual blockage. Hence propose to inject some system resorer into the blocked entry to the boiler via a flexible tube.
Presumably you've got a Mk II Netaheat (with two return tappings on the back of the heat exchanger (really smart place to put them!!). Looking at the layout, I guess it makes no difference whether the boiler is in a corner or not - you'd never be able to get at the return pipe(s) anyway.
But given that it's a cast HX, there must be space inside to place and afterwards remove the cores that form the water passages. There's certainly a coverplate on the left-hand side of the HX. Remove that and you just might have access to the ends of the return pipes from the inside. I'm not advising this - I've never removed one of those plates! But if the alternative is to scrap the boiler, it might be worth a try. If the boiler is in a left corner you're in with a (small) chance.
If you need to find a tradesperson to get your job done, please try our local search below,
or if you are doing it yourself you can find suppliers local to you.
Select the supplier or trade you require, enter your location to begin your search.
Please select a service and enter a location to continue...
Are you a trade or supplier? You can create your listing free at DIYnot Local