Just tackled electrician,she says because 2.5 T&E is passing thru wall(less than half a metre)i need 4mm cable because of
voltage drop.Also need 32A MCB replacing with 20A MCB in CU.
After advice on here went ahead and changed cooker point to 13A FCU to power shed(one 13A
double socket +5A FCU for lights).
Had a house wiring check done,electrition? said i wasn't allowed to do that and disconected wiring,who's right?
We use a gas cooker so have an unused cooker point.
My question is,can i replace the cooker point with a 13A FCU to power shed
which is thru the wall 1/2 a metre away and replace 32A MCB with 16/20A in CU.
I'll be using 2.5 T&E.
Hi all,
I need to replace a blown neon in a fcu.
My question is, does the wire with the resistor go to the positive or
negative terminal or doesn't it matter which way round it goes?
Thanks.