  1. O

    Central heating circulator and cycling

    If it cuts out and restarts instead of running continuously and you are still warm, then you are saving. At a lower setting, the circulator is not clearing the heat in the heat exchanger so it cycles until return water lowers the boiler. As long as you are warm enough, boiler cycling will save...
  2. O

    Testing oil boiler burner before system fill?

    What do you mean by testing? A quick couple of minutes would probably do little harm, but as the thermostats would not be active, longer running could be very detrimental, even dangerous.
  3. O

    Oil Boiler Won't fire after service

    Have you had a delivery of oil since the service? If so, you may have disturbed the sediment in the tank and sucked this through. You need to thoroughly purge the oil supply from the tank, through any filters (cleaning/replacing them ) and not forgetting the filter in the pump. All this should...
  4. O

    Rayburn 368k Glow Coils not lasting

    Anything 386K is expensive. The Glow plug lights a small reservoir beneath the thermocouple, and once that is hot, the ignition circuit is shut off and the main solenoid opens. It takes time for the flame to build up. You also need to ensure the flueways and fan are clear. Blocked flueways...
  5. O

    Rayburn 368k Glow Coils not lasting

    Have you checked the ignition transformer voltage? When flame established, does the current cease from the transformer? Either situation will overload the element and produce the result you have. Time to get the multimeter out.
  6. O

    Drain valve leaking and need help confirming replacement

    If you want to try something other than replacement which would require draining down, scrape off the crud, loosen it slightly and clean out as much as possible, then pu several winds of ptfe round the exposed thread and retighten. This could last until the time of year is more favourable.
  7. O

    Villager gas stove/fire replacement thermocouple

    https://www.fireboxstoves.co.uk/product/arada-spares/OBSOLETEThermoco-SAA7480?srsltid=AfmBOoomoOzd0q4C5p50NJU51SzEeCUTNwMNfnWANACeBOSORY4vDU6i Have you tried these?
  8. O

    Leaking pipe

    The pressure relief valve is leaking.
  9. O

    Oil Heater Issue

    With your set up, a vacuum pump attached to the oil feed into the tiger loop would be most useful. They are reasonably priced here and consist of a 2 litre vessel to which a hose is connected to the pipe, and the vessel is then evacuated by a manual pump. Depending on the length and rise of your...
  10. O

    Fixing Y Plan/Honeywell V4073A design flaw

    Many modern programmers will switch off the power when programmed to off.
  11. O

    Worcester greenstar danesmoor 12/18 oil boiler

    'Adjusting the pressure' without knowing what to and balancing off the air supply is a recipe for a soot disaster.
  12. O

    Potterton "Kingfisher CF60 CAT 1N" temperature controller replacement

    Your old thermostat would have ranged between approx 50c to 80c. Decide what flow temp you want in your radiators and set your new unit to that. The old stat was a relatively coarse unit and would have cycled the boiler over a range of approx 10-15c, I can't see any specification for the ST3008...
  13. O

    Grant Vortex Pro loud click in operation

    Could the click be a pressure release valve operating? How is the pressure gauge reading? Is there any discharge from the valve?
  14. O

    Atkinson Tankmaster valve (mk 1) - plugged end?

    If you buy a complete new gauge, I think you'll find that you can leave the tank fitting in the tank, with the tap turned off and the new valve fits onto it solving the pull to read problem and the gauge question. If you still want to use the old valve and just use a new filter then the best...
  15. O

    Hotspur Oil Boiler

    A yellow flame around the base suggests air supply problems .
  16. O

    Worcester 20/25 boiler transformer

    Follow the wiring diagram in the manufacturers instructions. You may have a post purge unit fitted to your burner, Worcesters often did, which slightly alters the position of connections, although IIRC, it does not affect the transformer. There is another diagram on the base of the control box...
  17. O

    Riello burner locks out after short purge time

    Glad to hear the finish. When any of us offer advice about regular servicing we are often shouted down, but this proves the case. Although you say everything is clean, this is not necessarily a good thing . It can be a symptom of lean mixture, which could explain your original problem when...
  18. O

    Worcester 20/25 boiler transformer

    That is the telephone response to the tooth sucking intake of breath that you would have got face to face.
  19. O

    Riello burner locks out after short purge time

    There is always that possibility, and persistent attempts at reset will not have helped it. My first suspicion would be the solenoid coil as the box looks for circuits in the startup period, and if there is a problem there, this is how it could show up.
  20. O

    Worcester 20/25 boiler transformer

    The transformer is connected to terminal 3 of the wiring base. From you picture, something has scorched the earth wire which needs investigating. The transformer can be tested by taking the live connection direct to the mains feed. Switch off all power to the boiler, connect the transformer...