  1. N

    Main Earth question with pics

    Ah, no its not. He's got his own cutout. The middle flat is using the landlords PME & its on the same supply as the flat I'm working on.
  2. N

    Main Earth question with pics

    Went to a job today to disconnect the storage heaters & add a supply for a combi in a property that was huge to say the least. (The ceilings were 4 metres high & then there were 2 staicases to each floor). It had been converted to 3 flats (one on each floor). I was working on the top flat...
  3. N

    Cant find where the Main Earth starts

    Thanks for the replies :wink: Phoned the DNO today who said the incoming tails are on a "wall loop" from next door but they couldnt give me a definate answer about the Main Earth. They have said I should put an Earthrod in & make it a TT but I am still unsure how this 6mm wire is connected...
  4. N

    Cant find where the Main Earth starts

    There wasnt any main bonding. I'm adding a cooker circuit so I'll make sure everythings up to spec. Do you think its worth giving the DNO a ring anyway ? Thinking about it, If this is a TT, the CU is an old MEMERA with rewireable fuses :?
  5. N

    Cant find where the Main Earth starts

    All I can see is 2 black wires (16mm) coming out the wall in metal conduit, the Live goes into the main fuse & then to the meter in 25mm. The N goes to a henly block & then to the meter in 25mm. Both then go to the CU There are no earth wires attached anywhere, except for this 6mm in the CU...
  6. N

    Cant find where the Main Earth starts

    Its end terraced. Meter at ground floor level, about a metre from the floor. Not sure about DNO providing PME. I'll have to ring them in the morning Thanks
  7. N

    Cant find where the Main Earth starts

    Went to look at a potential job & could not find where the Main Earth started from. It was quite an old house & the DNO's tails (2 x 16mm)looked like they were coming down the wall in metal conduit. There was about 2" of conduit showing. There was no evidence of overhead lines. I selected the...
  8. N

    Do you have to install supp bonding on new CU to 16th

    Do you think if I fitted a Split load board & put the upstairs lights including bathroom lights on an RCBO & the shower on the RCD side it would be ok not to carry out supp bonding ?, just a thought ? :?
  9. N

    Do you have to install supp bonding on new CU to 16th

    Sorry about another supp bonding question, but is there a reg to say you have to install supp bonding when changing the cu to the 16th? I have been doing it but just looking at a job that could be very difficult All other bonds up to spec
  10. N

    What do you think of this wire ?

    I did a search before posting aswell :wink:
  11. N

    What do you think of this wire ?

    Yeah saw it in the mag & on hmm, another forum Never heard of it before
  12. N

    What do you think of this wire ?

    Seen this advertised. Might get round a few RCD issues. http://tpwcc.com/index.html
  13. N

    New CU, RCD tripping when resetting CB

    Well.............. I still dont know This is a good example of people not regarding a fault as serious. Because its been working for the last 15 years they think its ok. I had a phonecall at 7.45 this morning & was told not to come today.
  14. N

    New CU, RCD tripping when resetting CB

    Just before I left tonight I was looking around the kitchen cupboards & noticed a piece of wood which looked like the back of the cupboard. I pulled it forward and there was an extension lead full of plugs behind it. Didnt have time to do anything else so I'll have a better look tomorrow. Thanks...
  15. N

    New CU, RCD tripping when resetting CB

    neutral in correct bar, i double checked If it was a borrowed neutral, I guess I would dissconnect all the neutrals & connect the problem circuit only to see if it tripped the RCD ?
  16. N

    New CU, RCD tripping when resetting CB

    Changed a CU today. Switched it back on & the RCD tripped when I reset one of the Ring CB's :evil: . I admit I only did a r1,r2,rn test (0.50, 1.48, 0.52) & an IR test (P+N joined & tested across to CPC). on this circuit (& the others). I know I should have done a proper PIR, but this time...
  17. N

    EIC TT querey

    Did a test on a new installation which was a TT. Not done a TT test before. I used my EFLI tester to measure the earth electrode resistance, same as doing a Ze test (which was 69.4ohms) Just filling out the EIC, do I put n/a in the 'Electrode resistance, Ra' box & put my result in the...
  18. N

    Going self employed - any advice

    oh yeah...... doh :oops:
  19. N

    Going self employed - any advice

    I went self employed just after Xmas 2008. A couple of things I'm glad I did was 1. buy all my tools when I had a job with money coming in every week & 2. had about 3 months mortgage sat in the bank for quiet times. People dont pay up straight away & cash flow can be a problem & you got to...