  1. C

    Worcester Econaheat Heatslave Combi; plane going down noise!

    Chrishutt is spot on , lost count of how many ive heard that try to be a lancaster bomber when the gas to water heat exchanger gets restricted/blocked ,three options ,clean out the system 30% chance of working.replace gas to water heat ex 100% but only untill it drags in more debri from system...
  2. C

    ARGH! this is driving me potty!

    Whats the standing pressure. Ive had a sytem leak at standing pressure 28-30 mb but sound at below 21mb and transco tend to go by the book (ish)
  3. C

    Worcester 240 too hot

    The temp dial on the front is only for CH hot water is set on the board at 54dec C . The boiler should give a temp rise of 40degC at a flow rate of 9lts per min (9 lt flow restrictor fitted ) if your flow rate is low then the temp will rise above 54 but it should come back down ,if the modureg...
  4. C

    Worcester Bosch Greenstar 35i Boiler making jet noise.

    As said the greenstar needs the corect co2 settings and if out the boiler can Hoot. Dont wory about the service just call Worcester the service eng wont be too botherd about no proof of service but if its been noisy since new then you poss have low gas inlet pressure you require at least 17mb...
  5. C

    worcester 280 combi h/w

    280 uses a honywell gas valve so small spanners req to adjust but as said test it before changeing ,both corgi eng jobs. min is 2.0 max 14.0 if on NG
  6. C

    worcester 280 no dhw

    The diverter valve powers over to the ch position and rests in dhw mode so i cant see it sticking in the ch pos but it poss ,can you see the lever on the side of the valve move after a ch demand (takes 12 seconds). if the ch is off and you turn a hot tap on does it fire up.
  7. C

    Venting boiler

    Sorry but 80,000 btu and only 4 rads and you want to run the boiler on full ? ?
  8. C

    stockist of boulter buderaus boilers

    whats RF got to do with part L it will still provide an interlock. ?
  9. C

    worcester 280 combi h/w

    Very much doupt its the gas valve not modulateing as the 280 is not that responsive, more chance of poor circulation .The gas wont start to ramp down untill the hot water gets to above 55 degC so if your eng tests the hot water temp comeing out of the boiler while manometer atatched he will see...
  10. C

    Noisy 28 Cdi

    Pump overrun kicks in when temp at ch sensor is above 55c ,the noise is usually after the gas has shut down ,never had no pump overrun on a heatronic board , have had loss of power to the pump a few times (stalling) but that just comes with no warning in seconds.
  11. C

    Noisy 28 Cdi

    Pen..... You suspected a restriction in the gas to water heat ex, thats prob the fault as you may have noticed from my previous posts i only work on Worcesters,the g/w tends to get blocked more on open vented systems and often the feed and expansion pipe will have a build up of scale/debri on...
  12. C

    Can I have an unvented system?

    As a side point i thourght that an uv cert was only required when the capacity was over a certain size and alot of eficiant uv cyl are ,this info comes after contacting a manafacturer regarding external controlls .
  13. C

    Worcester 24i losing pressure

    Your pressure relief valve could be slowly passing to outside to check undo the connection under the boiler on the left hand side leading to the pipe that goes outside ,if water comes out then or over time (dish underneath ) it requires changing plus the auto air vent can pass slowly inside the...
  14. C

    Worcester Heatslave 9-24

    Its not classed as obsolete yet, still in stock at Worcester but around 7 differant variations depending on the age and model of 9.24 ..Ive worked on hunreds of 9.24s and never had the pipe leak just the fiber washers in the connections plenty of times, strip it and re fit.
  15. C

    worcester 24i boiler how to relite?

    If you look on the top of the boiler at the left hand side front you will find the overheat re set button, if the center cross has popped up then it has tripped,re set by pressing down, most common cause to trip is lack of system pressure ,should be at one bar ish
  16. C

    Worcester 350rsf

    The 350 got a couple of bad habits ,one is the main driver board can stick in an anti cycle untill you re boot the board the other is that the pilpot coil goes open circuit after a time (varies from 10mins to 4hours ) when it cools down it will go back to normal ,the trouble is you only have 7.5...
  17. C

    Red expansion vessel worcester 240 combi

    If you read one bar on the boilers pressure gauge then you were presuriseing the whole boiler, you need the drain off open then take the pressure from the air valve with a tyre gauge,but if you have water at the air valve then the vessel is kaputt. Its a corgi job to replace it as the gas valve...
  18. C

    gas reg prob

    Thanks Chris thats spot on. The trouble with gas regs is they tend to tell you what you can do as against to what you cant. Thanks again.Cog
  19. C

    gas reg prob

    I cant find the corect reg that states you cant put an open flued boiler in a bathroom,doing my head in, anyone remember the section its in ?
  20. C

    Worcester Bosch 240 rsf trips off

    If the hot eater temp is less than 30deg C above the cold at 9lt per min and the body of the heat exchanger is upto 80 then you have a blocked or scaled up water to water heat exchanger.All the normal poor circ problems can take place such as slow pump or blocked diverter valve and...