  1. bellairaphon

    water very hot

    The DHW temp is preset to 55 degrees. I would be getting the installer back first to go through his commissioning again. And if everything is ok but the temp is still too hot get the manufacturer out too it. Nath
  2. bellairaphon

    Room stat not shutting off heating

    Possibly or a back feed from the valve. Do you have a means of testing the voltage ( multi meter )?
  3. bellairaphon

    Vokera Compact 28se and Honeywell THR872CUK Wireless Stat

    But don't cut away! I meant to say.
  4. bellairaphon

    Vokera Compact 28se and Honeywell THR872CUK Wireless Stat

    Isolate the power. There's a terminal strip with about 5-6 choc blocks. Remove all the wires. Then locate the 2 black wires they are the T1 & T2 you have on your diagram. So one off the black wires goes to A, the other black goes to B. That's the switch wires done. You will have a L & N with the...
  5. bellairaphon

    Central Heating problem

    Faulty 3 port valve I'd say!
  6. bellairaphon

    Underfloor heating structure

    Remove the floor and put the insulation between the joists. Up to the height of the spreader plate as previously mentioned. If done correctly your pipe will sit level with the joist. You will be better fitting a ply lined oak floor as to stop warping. Nath
  7. bellairaphon

    cannot drain central heating system

    Isolate the rad your removing. Open the vent to release the pressure. Close the vent put a couple of towels under the valve. Then undo the nut if you have an extra pair of hands then get that person to cover the hole while you do the other side. Carry outside empty the drain the majority of...
  8. bellairaphon

    Vokera boiler problems

    Do the upstairs rads work at all? Nath
  9. bellairaphon

    Worcester Bosch 280 RSF

    Ok I'm wrong. First time for everything I suppose! ;)
  10. bellairaphon

    worcester 28 i thermostat

    If it's the 28i RSF the dial may off broken off in the potentiometer. Or if you mean the room thermostat then it's either turned up full on the boiler. Or the links for the ex controls are still in the board. Nath
  11. bellairaphon

    Worcester Bosch 280 RSF

    The 280 has a plate HE.
  12. bellairaphon

    Worcester Bosch 280 RSF

    Filter or plate heatexchanger likely culprits. Nath
  13. bellairaphon

    3 Port Valve problems

    Yes that's correct. It's the last tee to stop reversed circulation when your hw is on. If that is the case it's just a matter of swapping the 2 pipes across. Nath
  14. bellairaphon

    3 Port Valve problems

    Flow and return wrong way round from the boiler.
  15. bellairaphon

    New gas supply. Connecting wood-burner back boiler into GCH.

    I'd get someone else in as your mate dosent even know how to pipe size. Mates rates don't always work out cheaper. Nath
  16. bellairaphon

    3 Port Valve problems

    Yes the valve should off been put before the 3 port then linked to the boiler return. Even tho not needed. Shut it off snd it should be fine. Nath
  17. bellairaphon

    3 Port Valve problems

    No the 22mm above the pump is used for expansion.
  18. bellairaphon

    3 Port Valve problems

    If you felt the bottom pipe in the cylinder does that become warm before the AB. It's starting to sound like a piping fault.
  19. bellairaphon

    3 Port Valve problems

    If you leave the hw/ch turned off till the pipes go cold. Then turn the hw on which pipe gets warm first B or AB?