  1. A

    TRV Head Identification

    I think that is a Wickes 'own brand' one about 20 yrs ago. I've just replaced one on my own system that was leaking around the pin.
  2. A

    Post the best photo you took today

    My local park this morning .... (edited to fix a bad upload)
  3. A

    Confused about how to do this

    A ~200W SMPSU, the initial in-rush to fill that capacitor would be alot more than 2A. I wouldn't be surprised to find its in the order 50A for a few mS.
  4. A

    Confused about how to do this

    Nope. You have gotten a little confused with the calculations. You are right that 180W @ 24V is 7.5A BUT ... it is the power which is the constant..... so 180W @ 230V = 0.78A (ignoring losses & assuming your 230V to 24V converting widget is 100% efficient.... which it wont be.... but 0.8A will...
  5. A

    Old Electric Meter

    From the second & third digits of the serial number? I'll have to go look at our Sangamo meter...
  6. A

    Regulations Myths

    Another good one must the the myth about not using the armour of SWA as the CPC or the cutting back of the outer sheath of SWA to fit a BS951 clamp onto the armour....
  7. A

    Dodgy earth… well no earth at all

    Not so much 'old'. Its still perfectly acceptable to use threaded steel conduit & trunking systems as the CPC even on new work (with certain provisos like link wires between socket boxes & socket fronts, as well as bridging straps across trunking joins & THREADed steel conduit not slip joints)...
  8. A

    RJ11 pinout

    I think you may need to do a little reconfiguration. If you disconnect the incoming BT pair & replace with the two wires coming from the router, the master socket will generate the bell ring wire & all should be well.
  9. A

    RJ11 pinout

    All of the RJ11 phones connectors I've ever seen have been 2 wire. Never seen the third, bell ring, wire implemented on a RJ11 - I guess the phone derives the bell ring internally.
  10. A

    Is it safe to change this molded American plug (electric kettle) ?

    Its not American, its AUSTRALIAN. The Oz plug is like the US one but has the blades twisted. Australia uses the same system that we do.... 240V 50Hz. So you could cut the plug off & fit a UK one. However, I am suspicious that most the that rating plate is in Chinese but claims a CE mark (which...
  11. A

    Choc blocks behind a light fitting

    The 'black thing' buried in the ceiling looks likes a conduit BESA box to me?
  12. A

    Two-Gang for One-Way & Two-Way?

    Yes, On the switch you wish to be 1-way..... just connect to the 'COM' & 'L1' terminals. leave the 'L2' terminal unconnected.
  13. A

    Wifi, faster than wired

    That router only has 10/100 Mbps ports! You need one with 1 Gbps if you want full throttle :-)
  14. A

    Single Phase ? does this look right?

    But, in this case, it doesn't matter. The device doesn't use the line-line voltage (since, if it did joining L1 & L2 together wouldn't be an option) so from either system (3 phase or split phase) the phase to neutral voltage is still 230V. The only thing which changes is the current in the...
  15. A

    Single Phase ? does this look right?

    Not sure I've ever seen a cable that has a current rating on it...... number of cores & cross-section - yes. Voltage rating - yes... but never a current rating. I read 450/750V rating & its type H07RNF. Where do you see a current rating?
  16. A

    Single Phase ? does this look right?

    Hmmmm... but that could lead to the neutral being overloaded (since there will be no cancellation between L1 & L2) What cross-section is the flex?
  17. A

    Over voltage

    Well yes, kind of & no. Solar installations feeding into the grid do cause a local rise in voltage but not because they are delivering a higher voltage than the mains (thats not how they work. This is AC land & things behave a little different from the DC case. There are other ways to push...
  18. A

    Why black cable with earth

    As EFLImpudence correctly states, It is good practice to connect unused conductors to earth.
  19. A

    Can anyone tell me what this is?

    I guess it could be a take on the "Willis" immersion heater? The electric showers of the day were only around 4 - 5 kW so, with two (3kW?) immersions it would have had an impressive 6kW capacity - it could have been an early 'instantaneous' water heater.
  20. A

    Emergency shut off valve to gas meter

    So thats raised my curiosity.... How do they change the ECV on alive gas service? I doubt they are gonna turn off the gas to the whole street considering all the fuss to purge all the lines & relight all pilots etc.....so how is it done?