Search results

  1. H

    Heating only comes on when HW is also sellected

    Update as follows: Checked wiring once I got my head round S plan wiring, and you were spot on the Mid position actuator is not opening on call for CH. Will fit new one next week and update. Thanks for your advice.
  2. H

    Heating only comes on when HW is also sellected

    Now you mention it I have replaced the rod/cylinder stat before, I will get up in the loft tmoz and check it and also look at the 3 port valv and relevent wires you have pointed out. Thanks for your advise will report on my findings.
  3. H

    Heating only comes on when HW is also sellected

    Yes worked alright up till now. The system was installed 5 1/2 years ago when house was refurbed, we have lived here for 4 years now. Had a warranty call after 18 months and Baxi replaced a part FOC, other than that been fine. Stat operates fine, turns off when at desired temp etc. I...
  4. H

    Heating only comes on when HW is also sellected

    Hi all, my problem is the CH is not coming on when selected on its own. The boiler is a Baxi Solo HE condensing boiler and it only comes on when we selct HW as well, obviously we dont want to waste energy/money heating water when all we want is CH. We have a room stat and regardless of...
  5. H

    Mixer shower not hot, cartridge or not??

    After reading more threads my update is: Cannot remove the cartridge and I am conviced this must be a plain mixer? :? I have now bit the bullet and checked the hot inlet filter, yep there was some limescale and crap, cleaned it out ,proved hot water through it, which should clear any...
  6. H

    Mixer shower not hot, cartridge or not??

    Help!Wasted another few hours on this now, I cannot remove the thermostatic cartridge. Found installation instructions on Showerforce website ' remove black plastic ring and unscrew cartridge'. BS, I cant shift it! I am now thinking blocked filter in the hot pipe, that will be fun as the...
  7. H

    Mixer shower not hot, cartridge or not??

    Yes it is, sorry for the delay been offline, BT prob. I think i have managed to turn the cartridge/valve so that the hot water inlet is now blocked as all I get is cold water. I dont actually know how I did this, other than removing circlip and turning the dial until it went loose, now you...
  8. H

    Mixer shower not hot, cartridge or not??

    Evening , could anybody point me in the right direction of how to resolve a cold mixer shower. Its Showerforce kit, I have 2 in the house, 1 is never used and is red hot works as it should and the other is used every day by 3 people and runs warm only, or did till I messed about with it and...
  9. H

    Haus WQP12-950G factory reset

    Anyone advice on the factory reset process on a Haus WQP12-950G. The dishwasher shared a cold feed with a washer via a 'Y' splitter that decided to bounce itself out of its slot, lock the drum up, bust the door off and snap the inlet pipe off and flood my sisters kitchen.The d/washer was on...
  10. H

    Square D loadline 60947-2 Max Zs

    Hmmm.... Typo it is CDAE34032. So it is not an SFA MCCB as that is single pole? :oops: Do I interpret the 'C' in the table as all ranges beginning with 'C', so 'CD' is 'C'? :? If so then its 1.33 for 5 sec ???
  11. H

    Square D loadline 60947-2 Max Zs

    Got it! see link below, page 24 for Zs info on Square D I line 60947-2 MCCB's. http://www.bizflips.com/library/pdf/Schneider/square_d/SQD5259_I-Line.pdf According to this I have the CD range MCCB which is a COAE34032 which is the SFA range. The table on Page 24 gives a Max Zs of 1.12 @ 5...
  12. H

    Square D loadline 60947-2 Max Zs

    Sorry ,for the delay, I was back there Friday and it is a Square D I Line board, see pics below Thanks
  13. H

    Square D loadline 60947-2 Max Zs

    Can anyone advse me on the max Zs for a triple pole 32A Square D Loadline 60947-2 MCCB I have seen some earlier posts from 2008 but the Zs is not given. Last resort I will have to ring Schnieder..... :|
  14. H

    BS 60947-2 max permitted ZS, any ideas???

    Hi mate do you still have this table for 60947-2 Square D MCCBs? I am after 32A triple pole Thanks
  15. H

    Meter box rules and a reg ref?

    Yes the inverters have transformers for total segregation of AC/DC, and yes type B RCD is the guidline from the Dti guide, the company I work for opt for type B RCBO's. Back to the original post is there a reg/spec/guide specifically for do and dont's in meter boxes?
  16. H

    Hot taps but warm shower

    Cranked up the setting on the boiler and eureka, hot showers!!! The missus is now banned from touching the dial on the boiler, it was turned right down! :oops: Thanks to all for your input, of owt changes will let you know
  17. H

    Hot taps but warm shower

    Sorry when I say off the cylinder I mean from the cylinder/header tank system, as i said in original post this is a Centercyl 85 without the shower outlet. More pics of system if reqd.....I have 2 tanks above cylinder, presumably for CH and hot water???? Both have isolating valves (red...
  18. H

    Hot taps but warm shower

    Thanks Hugh, See pic of mixer, how the heck do you get these off? There is a small hole on the dial, does this realease a circlip or is there a grub screw in there. In the loft it is plumbed in grey plastic no copper dropping down the cavity to the shower mixer straight of the...
  19. H

    Meter box rules and a reg ref?

    All relvent supply characteristics have been assessed, thats not a prob thanks. As a company we fit RCBO's on all PV inverter ccts. Its also there for overload & fault protection on the externally routed swa feeding the inverter 70mtrs away in a remote building. Otherwise I would have the...