  1. R

    Heatslave 2 hive single channel

    All sorted. Thank you very much guys!
  2. R

    Heatslave 2 hive single channel

    It does seem to be something that a jumper could solve rather than jamming multiple wires into single wire terminals. Heating now fires! I think I’m correct in restoring the factory link from boiler L to boiler LR tap.
  3. R

    Heatslave 2 hive single channel

    Ah I see. Thank you. So do I restore the link between L and LR (tap) on the boiler?
  4. R

    Heatslave 2 hive single channel

    Thanks @ianmcd ! So the common isn’t used on the boiler side?
  5. R

    Heatslave 2 hive single channel

    Is this what I need to do?
  6. R

    Heatslave 2 hive single channel

    Hi all Looking for some advice in connecting a hive single channel to a new heatslave ii. Everywhere I look suggests the common (black) should connect to ‘LS’ which I don’t have. If I connect to LR water, nothing happens. Do I need a jumper between common and live? Thank you
  7. R

    Replacement boiler, hybrid or woodburner

    Well I think time has finally come to admit defeat with the heatslave… (the highs and lows of my posts may make for a funny read one day). Multiple people have looked at it and can’t get a stable burn out of it. So I’m looking at replacements like-for-like but also considering a hybrids like...
  8. R

    Heatslave 12/18 ignition fire cycle

    just a quick update. Managed to get a number for a well recommended local engineer. After a bit of head scratching he found the burner gasket was missing and the condensate trap was full of debris (probably from when it was over fuelling a year or so ago). He tightened the burner up (I’ll...
  9. R

    Heatslave 12/18 ignition fire cycle

    Limped it along yesterday between other commitments but it’s back to the fire ignition cycle for a while before kicking in properly. I’ll have to check flue manifold tonight after work. I thought the bypass had corrected it for the short term but I think it’s another problem. Muggles, you...
  10. R

    Heatslave 12/18 ignition fire cycle

    Morning all. Thank you for the responses. I have a new capacitor turning up Monday so will fit that. In the meantime I disconnected the air feed from the flue and let it draw from the room. Fire, ignition cycle seems to have stopped which is a step forward. The boiler still has my original...
  11. R

    Heatslave 12/18 ignition fire cycle

    After a brief success with the boiler it’s thrown up another issue. During this cold snap the boiler fires up briefly, burns and then about about a minute it goes back to ignition stage. The cycle carries on; ignition, fire, ignition, fire… until I’ve had enough and shut it down. Oil flow seems...
  12. R

    Dry tiger loop

    Bit of an update. The boiler worked intermittently for the rest of the year. Because of other factors I didnt get a chance to get to the boiler - just nursing it along. Anyway, Thursday morning we woke up freezing. Friday I couldn’t get the thing restarted and the pump was making a horrible...
  13. R

    Dry tiger loop

    Thank you everyone for your responses! A lot to read up on. I think I’m going to buy a few lengths of 10mm copper and replace everything from the tank to the flexi. If nothing else, it’ll be a neater job. Very interesting to read about the positioning of the TL outside and the height in...
  14. R

    Dry tiger loop

    Hi John Do you mean the fuel feed after the loop? Between the pump and the loop?
  15. R

    Dry tiger loop

    Thanks both. With regards to the loop should it be like the old one on the wall? I have noticed it smells a lot more of kero since these works were done. It’s an out building so I haven’t really worried about it. When I use the wet vac it just pulls it straight through. The loop stays empty. I...
  16. R

    Dry tiger loop

    Hi Oilhead Thanks for the response. I’ve attached a photo which hopefully should answer your questions (excuse the mess). I believe the burner is top mounted, facing down. Working from the tank everything is clear, filters fine. I can pull plenty of oil through with a wetvac (I don’t have a...
  17. R

    Dry tiger loop

    Hi all I’ve had a number off issues with my heatslave 12/18, most recently returning from holiday to find it on lockout with a totally dry tiger loop. I managed to get it working again by priming the pump via a temporary gravity fed supply. It was then able to draw through oil from the tank...
  18. R

    Heatslave 12/18 lockout when cold

    Checked the control unit and it was giving the fault code short flash and four long which gives the cause as “within lockout safety time. No flame establishment”. Ive checked the photo sensor and given it a wipe over but it was spotless.
  19. R

    Heatslave 12/18 lockout when cold

    Hi John It’s a bentone dko 970 21 which give me google search results as satronics and Honeywells. do you know if there’s a way to test the control box or is it a case of replace it and see? with regards to the photocell I wonder if it beltching black smoke before the repair has messed up the...
  20. R

    Heatslave 12/18 lockout when cold

    Thank you for the responses. Photocell was replaced recently as the previous one ate itself. With regards to control box is that the clear burner control box? I’ll check if the engineer tested with an analyser. I know after his first visit it really smelt wrong. Now it’s smelling fairly sweet...