Ariston 28 RFFI Boiler not firing - Fan Pulsing

Joined
24 Feb 2008
Messages
29
Reaction score
1
Location
Leeds
Country
United Kingdom
Hi all, I have an Ariston 28 RFFI Boiler that won't fire up. When the Boiler switches on the Fan is "pulsing" i.e it spins up to speed then the air pressure switch operates then it cuts out, air pressure switch then drops out then fan spins up again repeatedly.
Because of this the boiler won't start the ignition sequence.
If the air tube is removed from the fan, the fan runs continuously but no ignition phase due to the air pressure switch not switching.
Anybody got any advice or thoughts ?
 
Sponsored Links
Hi all, I have an Ariston 28 RFFI Boiler that won't fire up. When the Boiler switches on the Fan is "pulsing" i.e it spins up to speed then the air pressure switch operates then it cuts out, air pressure switch then drops out then fan spins up again repeatedly.
Because of this the boiler won't start the ignition sequence.
If the air tube is removed from the fan, the fan runs continuously but no ignition phase due to the air pressure switch not switching.
Anybody got any advice or thoughts ?

Problem Solved, Fan Relay on PCB CBM2 not switching to hold Fan on after Air Pressure Switch had operated. PCB changed and now works.
 
Hi all, I have an Ariston 28 RFFI Boiler that won't fire up. When the Boiler switches on the Fan is "pulsing" i.e it spins up to speed then the air pressure switch operates then it cuts out, air pressure switch then drops out then fan spins up again repeatedly.
Because of this the boiler won't start the ignition sequence.
If the air tube is removed from the fan, the fan runs continuously but no ignition phase due to the air pressure switch not switching.
Anybody got any advice or thoughts ?

Problem Solved, Fan Relay on PCB CBM2 not switching to hold Fan on after Air Pressure Switch had operated. PCB changed and now works.

Hi, thanks for the heads up, I also had the same fualt on my Ariston boiler, checked the fan and the flow DP switch, all working OK. Suspected the PCB however after reading your comments, confirmed what I was suspecting. Replacement board arrived, fitted and all OK again. Great tip and thanks. :D
 
Sponsored Links
Huge thanks for this, same problem. My gas engineer tried to persuade me to replace the boiler for £2k saying a new PCB might come to as much as £400 to replace.

I wasn't convinced by this and fortunately checked for parts in local supplier for boiler spares, £80 ex VAT. Then I came across this post and realised I might be being taken for a ride! I noted at the same time that most parts for this boiler are fairly cheap to obtain, so if you have an engineer trying to charge you top dollar for genuine parts, check them first on the internet, most places will deliver within 24 hours if you can't find a supplier locally and so you could save yourself a fortune!

Ariston upgraded the spec of the PCB if you have a 2000-2004 model, so there may well have been problems with the original board, certainly the new one seems to make the boiler run much smoother.

The main PCB is very simple to fix yourself, just treat it with respect and care. Please remember to turn off the boiler electricity supply with isolator switch before doing anything. Unscrew the front, and remove cover to reveal PCBs, unplug the five connecting plugs (remember which socket the earth goes to and which the black lead goes to - I usually photograph these things with my phone before unplugging so I can remember what goes where). Unscrew the broken board and screw new one into place, and reconnect wires. Turn boiler on and it should start again fine, mine did anyway.

Once again my thanks to those who posted above - this is what the internet is for!
 