Earthing metal light fittings

Joined
28 May 2012
Messages
6
Reaction score
0
Location
Wiltshire
Country
United Kingdom
I'm struggling with some of the advice I'm finding on the net. Hopefully someone in the DIYnot community can set me straight!

I've got new metal light fittings (flourescant ceiling batten mounted) in my garage and in the fitting they have an earth in the connecting block, which is also connected by a tongue of metal from the chassis of the light.

I've seen mostly advice saying the fitting should be earthed, but some contradictory advice saying metal light fittings shouldn't be earthed.

As the fitting has the earth connection I'm tempted to connect it - Can anyone tell me if this is right or wrong thing to do?
 
It should be connected. May be a good idea to check that the garage itself and other metal fittings are earthed.
 
Yep, I've done a Zs test (0.48) which I think gives me a good earth reading.

Thanks guys.
 