Is this bad!! And does it need changing
Is this bad!! And does it need changing
The lighting circuit is on a 6A MCB, running totals of 14 LED spots (5.5w each so I guess thats 0.32A) and 4 energy bulbs at 8W each (so 0.13A)
Hi,
Ive just measure the current being pulled with all light on and its 0.55A (so wasnt to far off on the calcs)
22%.
Jaccuzi Pump
This can be wired in to the ring mains, but again via a FCU. The FCU can not be below floorboard by regulations.
Based on this its more than likely easier to put the FCU down under that stairs, however this is also where the CU is, so shall I just wire this on its own independent MCB directly, or is this a waste?
There is nothing within BS7671 to say you cannot, but a number of other building regulation guides do recommend that immersion heating circuit should be separate from any other, on which is the "on-site-guide" which generally works very closely to comply to the requirements of BS7671 and other building regulations. Which I am of the opinion is good practise, although my opinion may not be one of which you would consider being helpful.so would this be the right way to do it
Shower Pump (In loft)
It is acceptable to wire the shower pump on to the immersion heater wiring
Almost certainly, as previously mentioned the manufacturers instructions is a vital document to follow with regards to this, so I would suggest a read through of them. If you do not have at hand/lost, then they are very possibly available for download.which I assume I should do do this via an FCU
Makes no odds providing the current capacity of the cable is rated (after any de-rating factors) greater than that of the device and manufacturers instructions regarding the heating element and the pump are followed., they may be instruction stating the fuse size to be used.Question - although thew immersion heater cable is very thick (cooker wire type) and can handle the 32A MCB, would you recommend I change this to a 16A MCB for safety?
That would be correct, as all accessories should be accessible.Jaccuzi Pump
This can be wired in to the ring mains, but again via a FCU. The FCU can not be below floorboard by regulations.
That is purely up to you, new circuits require building control's to be notified and that requires a fee and inspection. Unless you employ an electrician that can do this for you.Based on this its more than likely easier to put the FCU down under that stairs, however this is also where the CU is, so shall I just wire this on its own independent MCB directly, or is this a waste?
If this is something you have installed recently, then they need to be maintenance free boxes or connections.arrr b*****r, I may have made a mistake here, There are the odd standard junction boxes in places where carpet will be present, and while I have used cable clips to secure the cables in to the junction boxes, they still don't meet section 526, as you say.
It is advisable to replace them, but if the installation of the junction boxes date back pre-requirement, then there would be nothing in the regs to say you have to swap them out.I guess its better to have spotted it now though, I will replace them with maintenance free junction boxes.
If they accessible, they are accessible, not that I am one for trawling through insulation for the finding of them, might be handy if you could bring them above into a fixed visible location.Are the ones in the loft, that are cover only loft insulation, deemed as accessible, or will they need to be maintenance free also?
Wago cliam that their connectors are configurable to BS5733-MF, (not sure what they mean by configurable? They either are or are not!)Are chocboxes with Wago connectors deemed maintenance free, or should I use thr Ashley ones
What they appear to mean (per their documentation - see here ) is that certain types and combinations of Wago connectors, used on circuits within certain specified current limits and housed in a WagoBox (i.e. in total, the 'configuration') meet the requirements for 'MF'.Wago cliam that their connectors are configurable to BS5733-MF, (not sure what they mean by configurable? They either are or are not!)
Wago connectors, per se, could not be marked 'MF' - since, as above, they do not fulfill the requirements for 'MF' unless used in a certain specified way ('configuration'). Since October 2012, WagoBoxes have been available with an 'MF' marking (plus the 'extended instruction set' - per link above) - see here .But to comply to BS5733 and be considered maintenance free, they should be stamped MF, as yet I have not seen a Wago imprinted with BS5733-MF on it.
That's the real irony about all this 'inaccessible junction box business'. If they really are 'inaccessible', then no-one inspecting the installation is even going to know they are there!I think there might be 1 or 2 junction boxes that I wont be able top get to at this present time with out a complete room dismantle and carpet up, when it comes to getting a electrician to sign off the wiring in the house, would they be able to detect these?
If you need to find a tradesperson to get your job done, please try our local search below, or if you are doing it yourself you can find suppliers local to you.
Select the supplier or trade you require, enter your location to begin your search.
Are you a trade or supplier? You can create your listing free at DIYnot Local