Kitchen ring final feeding one double socket, washing machine, dishwasher and boiler.
Protected by a 32a MCB
I was testing continuity of the LNE conductors and was getting a really low a reading .
Turns out the two 2.5 t&e go into a 45 amp isolator, then onto the sockets.
The continuity I was measuring was the small loop from the board to the isolator.
I tested the end to end continuity of the conductors of the load side of the isolator and got readings I would expect.
I think this is known as a lollypop circuit.
So two 2.5 cables in parallel supplying a 2.5 ring final circuit ,
Protected by a 32 amp MCB.
Would like to know your thoughts on this.
Can throw you a bit when testing[/url]