So I've monitored my boiler this afternoon. It doesn't make sense...
So flow temp is 60C
Anti fast cycle flow temp is -14
Anti fast cycle time is 15 mins
12:00 - boiler comes on. Flow temp initially goes to 43C, then settles down to 30C and builds from there.
12:29 - reaches the 60C flow temp and continues at that for a while.
13:09 - hits 61C as one or more of the TRVS presumably reaches setting temp and starts to close radiator. The boiler has been running continously since it started and burning gas. House temp has increased by 2.5 - 3C.
13:19 - hits 64C. Boiler stops burning gas after about 30 seconds. Fine. It is from here that I am interested to see what the anti fast settings do. From the point it stopped burning gas it continues cycling for about 5 mins. Flow temp falls quite quickly to 59C.
13:23 - cycling stops. 57C. Boiler now idle.
13:29 - cycling starts again, no gas. Temp goes from 59C - 51C.
13:33 - cycling stops. 50C. Idle.
That's two 5 min cycles without gas, 5 mins apart.
13:38 - 50C, boiler fires up, burns gas. Temp goes to 58C quickly, but then settles down to 53C.
13:40 - gas stops, but cycling continues.
13:44 - 46C, cycling stops. Boiler becomes idle.
So this is the end of a third cycle without gas although the third one began with a brief period of burning gas. So about 15 mins of cycling. And the -14C point has also been reached...
13:46 - 47C. Idle.
13:50 - another cycle with no gas. Temp goes from 48C to 41C.
13:53 - the gas comes back on and now the boiler seems to begin again a proper burn back towards set temperature. Gets up to 56C by 14:00 before turning off with timer.
So I'd appreciate thoughts. It didn't seem to fire up at -14 below set temperature. Or fire up properly at -14 below SP+4. And it isn't clear how the 15 minute setting came into effect either. What was that mini burn all about at 13:38?
The anti cycle time, on this burn, will have been used up because of the length of the burn (about 1 hr 20 mins). so therefore it will be on the set anti hysteresis only.
The anti hysteresis drop is from the original flow temp (60-14=46)
Somebody may have just run some hot water just prior to the 12:00 start time therefore showing the water temp on the display (I've noticed this happens with mine)
13:19 is probably your pump still running for around 5 minutes
13:29 also sounds like the pump running
13:40 also sounds like the pump as no gas is being used
13:38 Sounds like you have hot water pre heat on OR did someone use a hot tap? If this is the case, there is a setting where the boiler lies idle for a certain amount of time after hot water is demanded (mine is set at 1 minute default)
Sometimes, when it is very near the temp drop of the anti hysteresis it doesn't show the exact temp. number on the display.
I'm assuming this is a combi and not a heat only boiler i.e. have you a separate water cistern that it is heating?