Sorry I miss understood. I used a lamp.Sorry, what did I ask? I know you got a shock from the toaster.
then should have tripped -
maybe the RCD has tripped and not showing as off
you have 2 RCDs with a SOCKETS shown on the label
is the shower working
just wonder if the RCD tripped BUT not shown as off on switch - not experienced that - so no idea if possible , but i know other switches can do that

is the fridge plugged into one of the working sockets and working NOW
everything in the house all sockets are working except for the 3 you shown in kitchen
its late now in UK - so you may want to leave
any frezers ??? - fish tanks or anything else that MUST have power overnight and they are working OK
I must have touched the metal inside the toaster, toasting compartment. I got a shock, the kettle on a different wall socket stopped boiling, also the sockets next it stopped working (Fridge)
its late now in UK - so you may want to leave
any frezers ??? - fish tanks or anything else that MUST have power overnight and they are working OK
so which switch was that - as you have sockets written on both sides of CUIve just turned off the downstairs sockets at the consumer unit.

As Pete says above.![]()
Also, any more hidden fuse boxes or fused spurs?
In kitchen cupboards, for example?

What's in that funny looking eye level cupboard next to the toaster?
I'd be surprised if it's anything to do with that. The fuse in that SHOULD be for the boiler only. Does the boiler appear to have power?Just found this under the boiler !
Any sockets before this fuze box works anything after doesn't.