  1. K

    My boiler fires up every minute, whilst working in full!!

    I managed to sort it out (for now at least!). It was the Air Pressure Switch. Had it replaced after seeing it overheated and somehow deformed as a result. Now everything working just fine. Thanks for everyone for helping me to sort this out. This is the like that really helped me to sort...
  2. K

    Myson Apollo 30/50si cutting out

    I had a similar problem and by reading your posts, I managed to sort out mine too! So, a big thanks first to 'Slugbabydotcom' for his professional advice and explanation and second thanks to 'davidrobertson' who put this into practice and got the result. Cheers Kavous
  3. K

    Myson Apollo 40S - Gas cut off

    Actually the pump sometimes makes some ratteling noise when works on high speed. Is there any ways to check if this is really faulty and if so is there any ways to fix it?
  4. K

    Myson Apollo 40S - Gas cut off

    thanks for the swift response. Unfortunately I don't have the equipment to do the measurements. However I will change the stats next week to see if it does the trick (I think they've been in service long enough!). One thing that I noticed was that when I set the pump to low (it's got 3 levels)...
  5. K

    Myson Apollo 40S - Gas cut off

    I'm having this problem for a while. Basically, when the temperature gets close to the set temperature, gas cuts off and boiler shuts off and after 1-3 seconds it fires off again and works for a short while and then the same story again. There are three thermostat on the water pipe (limitstat...
  6. Untitled

    Untitled

  7. Untitled

    Untitled

  8. Untitled

    Untitled

  9. Untitled

    Untitled

  10. K

    My boiler fires up every minute, whilst working in full!!

    I think this would be the case. Since I have realised that the gas wouldn't turned off unless the temp is close to set value, which, I believe, in a sense prove your point. I have a thermostat attached to the hot water tank (upstairs) -middle picture - which from your description wouldn't be...
  11. Untitled

    Untitled

  12. Untitled

    Untitled

  13. K

    My boiler fires up every minute, whilst working in full!!

    Tony, Your technical language is far beyond my understanding.... Can you tell me how I would be able to measure "the flow and return temperatures across the boiler"? Is the "boiler thermostat" the same as the room's thermostat (the one that we use to adjust the temperature in the room)...
  14. K

    My boiler fires up every minute, whilst working in full!!

    Yes! I checked all the radiators and also checked if they've got air trapped in but they were ok. As for pumps, they seem to be working fine, as I can hear them working all the time (specially I checked when the repeated firing up is happening they work as normal). Not sure how to check the...
  15. K

    My boiler fires up every minute, whilst working in full!!

    Sorry for the confusion... yes it is Myson :lol: .... Well... I have just found out what is really going on there!!! (doesn't sound good though). For some reasons gas cuts off and the boiler needs to fire up again so the ignition works and if the gas is supplied, it fires up and if not it...
  16. K

    My boiler fires up every minute, whilst working in full!!

    Boiler is 'Mason Apollo' and I have got a closed system central heating. Well..., when I switch on the boiler it fires up and works just fine. After a while say 5min, you can hear that the ignition works again as if the boiler is gonna start working) and it seems that it fires up again...
  17. K

    My boiler fires up every minute, whilst working in full!!

    Guys, Started 3 days ago. When the boiler is working (no matter if it's on HW or CH or both) after the first ignition, it keeps firing up every now and then say in less than a minute although the hole boiler is already working. I hoped I could pass this winter without major problem with...
  18. K

    Myson Apollo boiler: Loss of hot water

    The problem is still there :x , well... I have not replaced the BV but removed the thermostat inside and blocked the cold water coming into it (now it works like straight connection!!). Now, I loose hot water in seconds and it seems that the water coming out of tank gets cold very rapidly...
  19. K

    Myson Apollo boiler: Loss of hot water

    It's not really easy to say if the temp changes in the tank because of the isolationa etc. but I would say if there is any changes, that will be very little. Kav
  20. K

    Myson Apollo boiler: Loss of hot water

    Mick, Would the problem lies in the VB. Because when it is turned (technically speaking :wink: ) to the Max there is very hot water running from the tap but just for a few seconds and then it starts getting colder and colder till it gets to a certain temp and stays like that. As I've said...