Doing some dead testing on my house today, need some input on my results.
Downstairs RFC.
r1 = 0.55
rn = 0.54
r2 = 0.87
L+N Interconnect = 0.26
So those results are all fine. Very similar to the upstairs rfc and smaller than the shorter kitchen rfc
However, when interlinking L+CPC or N+CPC i get 30-50 ohms!
Would a still connected appliance cause these results? Because as far as I can tell I've unplugged everything but can't see another reason for such a high reading, especially with the end to end being fine.