Hi,

My Salus wireless room thermostat RT300RF has given up the ghost. I was recommended the Honeywell DT92E. Only problem is I am confused by the wiring.

The Salus was set up volt free-

Blue wire into N
Red into Live
Yellow into COM (volt free feed)
Black into NO (switched live)

Nothing was linked.

The Honeywell has 6 ports:
N L L ABC

Can you tell me what wire goes where?

Thanks
 
Sponsored Links
Salus - Honeywell
N. - N
L. - L
COM. - A
NO. - B
The 'Ls' in the Honeywell are linked internally so you only need one connected.
 
Salus - Honeywell
N. - N
L. - L
COM. - A
NO. - B
The 'Ls' in the Honeywell are linked internally so you only need one connected.

That has worked perfectly (you won't be surprised to hear). Many thanks indeed.
 