The SWA cable could be glanded into a metal box for mechanical strength with the metal box being enclosed in a plastic box to prevent access (without tools) to the "earth" imported along the SWA onto the metal box.
I would NOT put a junction in the box but would extend the uncut inner cores of the SWA cable out of the boxes to the CU or other device the cable is supplying. As the sleeve around the cores is not adequate mechanical protection for the cores I would add mechanical protection to the cores.
I would NOT put a junction in the box but would extend the uncut inner cores of the SWA cable out of the boxes to the CU or other device the cable is supplying. As the sleeve around the cores is not adequate mechanical protection for the cores I would add mechanical protection to the cores.