HW Cylinder. Thanks. Thinking about this as the CW tank in the loft is on the same platform as the small CH filling tank then if there was a leak in the HW cylinder coil this small tank would overflow due to the water level in it being far lower thn the CW tank next to it. Am I right?
If you have a thermostatic mixer shower or tap, I would be looking there first, coil pinholing can happen but is very rare , turn off the cold feed to the Cylinder, then open the mixer (shower or tap) and set to max Hot and if it keeps dribbling then you have what is called crossover
HW Cylinder. Thanks. Thinking about this as the CW tank in the loft is on the same platform as the small CH filling tank then if there was a leak in the HW cylinder coil this small tank would overflow due to the water level in it being far lower thn the CW tank next to it. Am I right?