Hi all,
I'm being asked to supply location data and overviews for an Zaptec Go EV charger install that the car dealer is providing. Before I point them at the desired location, I just want to ask if it's even worthwhile. I don't want to lead them on a wild goose chase.
All of this kit has been fitted within the last 5 years, and I'd like the charger to be installed on and fed from the garage consumer unit - but I have my doubts.
The house has a 100A main fuse, and a 40A RCBO supplies the garage, via 3x 6mm buried/ducted SWA. My understanding is that cable is good for 44A when buried, so the 40A RCBO makes sense.
The garage has a 1.5kW HVAC heater and a 2.2kW compressor (sockets circuit, 32A RCBO), plus the usual idle usage of ~200W when all the lights are on (lights, 6A). There's a car lift as well, hanging off a 2.2kW VFD inverter (20A RCBO - used to be lower, but startup current often tripped it).
By my maths, a 7kW EV charger would far exceed what the garage can supply, and am I right in thinking diversity doesn't count here because it's a workshop?
Are my options then a Zaptec Go with a sensing kit in order to dial it back when the garage is in use, or to find another location? Are these Sense features compliant enough to permit that idea?
Thanks for reading this far
I'm being asked to supply location data and overviews for an Zaptec Go EV charger install that the car dealer is providing. Before I point them at the desired location, I just want to ask if it's even worthwhile. I don't want to lead them on a wild goose chase.
All of this kit has been fitted within the last 5 years, and I'd like the charger to be installed on and fed from the garage consumer unit - but I have my doubts.
The house has a 100A main fuse, and a 40A RCBO supplies the garage, via 3x 6mm buried/ducted SWA. My understanding is that cable is good for 44A when buried, so the 40A RCBO makes sense.
The garage has a 1.5kW HVAC heater and a 2.2kW compressor (sockets circuit, 32A RCBO), plus the usual idle usage of ~200W when all the lights are on (lights, 6A). There's a car lift as well, hanging off a 2.2kW VFD inverter (20A RCBO - used to be lower, but startup current often tripped it).
By my maths, a 7kW EV charger would far exceed what the garage can supply, and am I right in thinking diversity doesn't count here because it's a workshop?
Are my options then a Zaptec Go with a sensing kit in order to dial it back when the garage is in use, or to find another location? Are these Sense features compliant enough to permit that idea?
Thanks for reading this far