Exported PME to a summerhouse (shed...) with a hot tub

TT with a reliable Ground electode and a reliable RCD are as safe as an experted PME "earth" when the PME is in full working order. But hazardous when the PME is compromised and Neutral is not at ground potential.
I think that's a bit ambiguous.

For the benefit of other readers, do I take it that you mean that a PME 'earth' (rather than "TT with a reliable Ground electode and a reliable RCD") is "hazardous when the PME is compromised and Neutral is not at ground potential" ?

Kind Regards, John
 
Sponsored Links
Yes I am saying that a compromised PME "Earth" is hazardous. There is a voltage difference between the PME "Earth" that forms the CPC and anything in contact with true ground.

Any current that flows from Earth ( PME ) to Ground does not pass though any over current protective device neither does it flow through any RCD or RCBO
 
Yes I am saying that a compromised PME "Earth" is hazardous.
Yes, I know you were - but, as I said, I think anyone who did not already know that would get the wrong impression by reading what you actuaklly wrote - so perhaps some 'clarifying editing' might be appropriate? To my mind, what you wrote is most obviously read as ...

" TT with a reliable Ground electode and a reliable RCD are as safe
.... when the PME is in full working order
.... But hazardous when the PME is compromised and Neutral is not at ground potential.
"

Kind Regards, John
 