Hi
BCO has come around for final sign off of loft conversion and has just noticed the open soil stack is only about 2.5m from a velux.
I know Regs H1 state it must be 3m otherwise you need to go 900mm above window so no arguments with the BCO!
He has suggested bringing the pipe inside the bungalow roof space and using an AAV. This seems insane to me as the pipe is currently outside and goes through soffit and tile to vent. It would cost a fortune to do what he says and make good, not even sure how you'd get the pipe in.
My question is what other options do I have? My only thoughts have been extending the soil pipe, which will need 2m of pipe sticking in the air!
Any help greatly appreciated.