So got a question for you all
If my supply to my shed is 32amp and the protected by a 40amp 30ma rcd could I use a 16a mcb for the sockets 16a mcb for a 16a blue outside socket and a 6a mcb for the light ... Even know the total is more then 32a supply
there will never be a full 16amp one the blue outside socket as the caravan is fitted with a 10amp mcb
The reason why I wanted to use a 16a supply for the blue socket is that I don't fancy the walk back to flip the sheds mcb when I would rather the caravan mcb to trip if I or the wife was to overload it