Is .75mm 5 Core Cable OK For Domestic CH Pump?

Could you all bear with me while I try and come up with a reasonable excuse for having missed that row of the table?
 
Could you all bear with me while I try and come up with a reasonable excuse for having missed that row of the table?
There's no need. There's very few of us who have not missed something at least as important as that, without any 'excuse', so we understand!

We may 'hold some things against you', but not this :)

Kind Regards, John
 
Bear in mind that when aptsys said "it's OK, only a few watts", that was before the 3A fuse had been stated. It wouldn't matter if the load was only a couple of watts (as is the case with motorised valves) - the cable has to be rated to suit the fuse in the supply.
 
Bear in mind that when aptsys said "it's OK, only a few watts",
It wasn't aptsys.

that was before the 3A fuse had been stated. It wouldn't matter if the load was only a couple of watts (as is the case with motorised valves) - the cable has to be rated to suit the fuse in the supply.
Not necessarily - but it is a CH system and it was verified in post #4.
 