My HW is fine, nice and hot and steady.
The CH is fine, but the boiler is only heating to 49/50 degrees, which makes the rads only slightly warm.
I have had 3 heating engineers round from British Gas.
New main pcb.
New pump.
Each time they have left and said to my Wife, “it’s fixed”.
When I come home I find it still has the same issue.
So I have done some basic investigations while I wait for yet another engineer.
When I put the boiler into chimney sweep mode, it goes well past 50, boiler is set to 75.
I thought it might be the Hive thermostat they fitted but the thermostat is constantly sending a signal to the pcb when on and switches off when off.
When in chimney sweep mode the rads get nice and hot, so the boiler is capable, but something seems to restrict it.
Any ideas?
Cheers
Iggy