non-maintained emergency light

Joined
30 Mar 2015
Messages
4,432
Reaction score
82
Country
United Kingdom
I have one of these and supplied it with a permanent live and neutral. I have removed the small wire between L and SL. Nothing lights up - not even the led indicator. I have waited 3 days, thinking it may be down to charging, still no led indicator. When cut the power, the light doesn't illuminate.

Thinking it may be a faulty fitting, I tried a second one and the exact same issue.

Can someone please advise.

1769525450301.png
 
Batteries for emergency lights usually have a short lead and a plug on the end which needs to be connected to the matching socket on the circuit board.
Yes indeed, they sometimes have a little DIL type switch on the circuit board so you can flick the battery on or off.
The instruction manual does not seem to give much info.
 

If you need to find a tradesperson to get your job done, please try our local search below, or if you are doing it yourself you can find suppliers local to you.

Select the supplier or trade you require, enter your location to begin your search.


Are you a trade or supplier? You can create your listing free at DIYnot Local

 
Back
Top