Shock Origin?

Joined
10 Feb 2007
Messages
1,399
Reaction score
42
Location
Cumbria
Country
United Kingdom
I isolated a CU the other day(flicked main switch), tested bus bar and it was dead! Changed over some fuseways and zing!! Got a belt!
One circuit was the garage cable, might there be a capacitor on something in the garage (detached shed). Thought that was the last of it and got another 5 mins later... :roll:

Would that have been a full 230v coming back to ground itself or less?
Only one distribution board.
 
What type of testers were you using?

What did you test the busbar to?
 
but what did you test the busbar to?

Earth, neutral, both and then tested neutral to earth aswell?
 
Is it possible that the live contact of the switch did not disconnect?

This would give you a 0V reading when testing live to neutral, when the installation is infact still live.

This is why you must always test every live conductor to each other AND earth.
 
Is it possible that the live contact of the switch did not disconnect?

This would give you a 0V reading when testing live to neutral, when the installation is infact still live.

This is why you must always test every live conductor to each other AND earth.
I will go back and re-test, looking for all possibilities in current paths.
 