Hmm that makes no sense to me
My under was that you don’t press any text buttons prior to testing with rcd tester
The tester shows how it will operate under fault conditions “as is” without prior freeing it up
I know the test procedure has changed, there was it seems a problem with some special RCDs when tested as we were originally taught. I will hold up my hand and admit I have not got a copy of the latest guidelines, but they are guidelines, and some skill is required when working out how to test RCDs as in the main they are in circuit when tested, to touch the terminal screws, means it needs retesting after, and it is rare there is an isolator after the RCD, So working out the order of testing, the ½ test, I suppose should be after the RCD has tripped once, but testing at full rating either the + or the - will be done after it has tripped once, so it makes no sense to require the tester to be used first.
In the main, I use the RCD tester because a RCD has been tripping, so I want to know if it is oversensitive, so the ramp test, and the clamp-on tell me if oversensitive or if a high back-ground leakage, and I can't understand why the EICR, Minor Works, and installation certificates do not record the back-ground leakage? Yes we know with a 30 mA RCD this should be 9 mA or less (30%) but seeing a rise would alert one to a fault, rather than it being normal.
I know the whole supply with nothing running, but items left plugged in with my own house is around 8 mA.

So I can see if there is something causing a problem, as I have a base line to work off. As it stands only 2 of the 14 RCBOs are double pole switching, so turning them off does not test the neutrals, but normally even with single pole switching you will see the back-ground leakage drop, so showing which circuit has a likely fault developing.
But the ramp test also helps

to work out what the real value is, one needs to add the clamp-on reading, but clamp-on was for all circuits getting the clamp around a single circuit means taking the cover off the consumer unit, the RCD test at 30 mA will tell you tripping time, but it does not show it will trip at 30 mA, with a background leakage of 9 mA it will only show it will trip at 39 mA.
But does it matter? If it fails to trip at ½ and trips at full, on 30 mA setting, then we know it will trip at between 30 and 45 mA if clamp-on not used.
I think on ramp test, my RCD tester uses 3 mA stages, I have seen 21, 24, and 27 mA but not any valve between them. But in the main we want the RCD to trip before we touch any live part, not within 40 mS after touching the live part, so being spot on 30 mA does not really matter.
We do the tests, but look at a schedule of test results, and we see 30 mA, what is the point of that? It may as well be a tick.