  1. I

    RCD tripping

    Space Cat, first thing this morning I purchesd a replacement RCCB and fitted to C/U1. Carried out the ramp check and 28mA, powered up heater circuits one by one and rest of circuits, hey presto no tripping and very small amout of leakage. Reinstated the hall and switched everything on and all ok...
  2. I

    RCD tripping

    Thanks for that space cat, 1 of the wiring faults I found was the lighting circuit had the switched live connected to the loop live in the 2 flo tubes in the kitchen which I corrected yesterday, checked polarity in the lights tested and then powered up ok. I have carried out a ramp test on the...
  3. I

    Placement of Cooker Switch - Rules/Regulations relating to

    "If your gunna quote it get right", that was the book I read info in but got my figure mixed up as 150 is distance from worktop. Sorry for any confusion.
  4. I

    Placement of Cooker Switch - Rules/Regulations relating to

    no set distance in regs but building regs state 150mm to either side of cooker. hope this helps
  5. I

    RCD tripping

    Thanks for reply. C/U 1 & 2 were wired at the same time, in 1998 I believe. The lighting circuits are all in C/U2 and seperate to C/U1. The main earth is not connected to a MET but looped across each C/U. Now you mentioned that "was the fault there before", when carrying out various other...
  6. I

    RCD tripping

    Hi, can anyone advise on where next to go please. I was installing a lighting circuit in a Village Hall. There is 2 C/U's, the one I was working on is not tripping, but no. 2 C/U has now started to trip on the rcd. It has 6 quartz halogen heaters on 3 separate mcb's , ring main and a burglar...
  7. I

    electric hand wash

    Could anyone please point me in the direction of where to buy an electic hand wash with an extended swivel tap of a distance of 400mm. I need to fit one to a kitchen with no hot water to feed two sinks. The sinks can be moved slightly to accomadate a suitable product. Many thanks to anyone who...
  8. I

    1.5mm twin and earth used outside

    Can someone please settle this arguement. Next door has had outside lights fitted in south facing rear of house. Cable is T & E clipped direct to outside of wall. I informed neighbour that this work is notifiable, should not have been clipped direct but protected with conduit and certificates...
  9. I

    Running cable to a shed

    A spur off the ring main sounds like your only option. It must be RCD protected. This is a notifiable job so don't forget to tell your LABC.
  10. I

    no continuity on live?

    I use the wandering lead method as I find it easier when checking continuity with the readings that I get back
  11. I

    Which flex to power a 230V~AC, 1phase 0.18/012A fan?

    use 3 core cable 0.75mm because fan may need an earth, picture not clear. Use sufficient length of cable to put 3 pin plug on. I only use crimps to extend cable as a last resort and definetly I don't use un insulated crimps. Even with heatshrink on the crimps I still woudn't trust them. It looks...
  12. I

    Light not working: Help

    Those voltages don't help much. Remove the light ceiling rose and repost what wires are in the rose and how many. This will help in what direction to send you in. In the switch there should be a red going into C and a black with a red sleeve on connected to L1. Have a look and come back.
  13. I

    SWA armour connecting

    Can anyone explain why in some installations and circumstances is the armour terminated at 1 end, both ends and what is the general ruling?
  14. I

    optima xm6

    Thanks for all the replies and tips. Only just got my computer back from shop and not been able to log on for a while. Once again thanks. I will remove the zone cable completely as wall is down. Not sure where to link out, as am I right in saying the reed switch has 2 contacts?
  15. I

    optima xm6

    Thanks for the replies, to answer 1 point it is in the county of Norfolk UK, I was up there again tonight and managed to disable the zone to allow the alarm to be used again. What cables or part of zone 4 circuit do I need to link to enable use and what is the recommended cable for burglar...
  16. I

    Extractor fans and armoured cable...

    I use a battery grinder with a .5mm cutting disc, goes through very easy.
  17. I

    To fit an electric shower...possible for an 'amateur'?

    From the question you have asked it shows you are not competant to attempt this. It is a notifiable job and must be done by a part P electrician. Do not connect a shower to this spare fuse as it will only be a small fire that burns your house down, you will invalidate your insurance by causing...
  18. I

    optima xm6

    Hello, can anyone help with advise on this problem, Local Scout hut I am involved in has just knocked down a stud wall and found cable inside stud so stopped. I had a look and suspect it is the burglar alarm cable. (I removed all the mains cable in the wall before they started to knock down and...
  19. I

    vivaro turbo 1.9 52 plate

    My turbo blew up last night, 2 on E bay. What do I need to be aware of when replacing turbo. RAC hero says intercooler will need flushing, any advise on what else I need to be aware of before I replace would be gratefully received. Is it a simple enough job? Many thabks in advance to all who...