Question for the electrically competent.
You are working in a property and establish a high Ze reading. 180 ohms. The earthing arrangement is TN-C-S. The seals are missing from the cut out and out of interest you remove the cover and find the link between the incoming neutral and installation earth is missing.
All circuits are protected by a 30mA RCD apart from lighting circuits. The customer is very elderly and it is the end of the day / early evening.
Would you:
1/ Isolate supply and advise customer to contact electricity supplier?
2/ Leave power on and advise customer to contact electricity supplier?
3/ Provide a temporary PME link and advise customer to contact electricity supplier?
All other solutions welcome.
You are working in a property and establish a high Ze reading. 180 ohms. The earthing arrangement is TN-C-S. The seals are missing from the cut out and out of interest you remove the cover and find the link between the incoming neutral and installation earth is missing.
All circuits are protected by a 30mA RCD apart from lighting circuits. The customer is very elderly and it is the end of the day / early evening.
Would you:
1/ Isolate supply and advise customer to contact electricity supplier?
2/ Leave power on and advise customer to contact electricity supplier?
3/ Provide a temporary PME link and advise customer to contact electricity supplier?
All other solutions welcome.