No. Determining if it is extraneous involves a measurement to the MET. ... Determining if it requires SB involves a measurement to other exrtaneous and exposed-c-ps in the location.
Yes, I obviously realise that, and was not suggesting that exactly the same measurements would be undertaken - but I was talking about what, in practice, is almost always (maybe just always!) going to be the situation.
In practice, if a pipe is an extraneous-c-p (to the location) that is going to be because it is in electrical continuity with a bonded pipe and/or because it is in electrical continuity with something (boiler, CH bits, immersion etc.) which is earthed. In either case, the resistance to the MET will be very low ('a few ohms' at the very most), hence the resistance between any two of those extraneous-c-ps will be 'twice very low' (essentially, still 'very low'). As for exposed-c-ps, to satisfy fault protection requirements, the resistance from any of them to the MET is, again, necessarily 'very low' - so, again, the resistance between any two exposed-c-ps will be 'twice very low' (essentially, still 'very low). Finally, it follows from the above that the resistance between any extraneous-c-p and any exposed-c-p will, yet again, be 'twice very low' (essentially, still 'very low).
As I went on to say, I'm not sure that (in deciding whether SB is needed) we have to take into account the possibility that the exposed-c-ps may have inadequate fault protection.
Not necessarily. Two CPCs might have considerable resistance from one ecp to the CU and back to the other.
Unless (as above) you think that one has to consider the possibility that one or both exposed-cps has pitifully unsatisfactory fault protection, I'm not sure where your 'considerable resistance' comes from. The Zs for each of the circuits concerned should be less than the 'max Zs' for the OPD concerned, so the max permissible resistance to MET would be Zs(max)-Ze. The maximum resistance between two exposed-c-ps which both have adequate fault protection would therefore be Zs(mas)1 + Zs(max)2 - (2 x Ze) - which, again, is 'very small'.
I just meant that most people don't consider the "simultaneously accessible" part - just bonding everything in the room - accessible or not, let alone simultaneously.
Oh, fair enough - in which case, as I said, I agree.
I've just thought of another possible terminological quandary. If a metal pipe emerging from (hence in electrical continuity with) something earthed (boiler, CH pump etc.) enters a bathroom, does it count as an extraneous-c-p or an exposed-c-p. If, as I suspect, your answer is the former, what would you say if, hypothetically (and for some bizarre reason), a bit of cable (rather than a pipe) were connected to the earth terminal of the boiler/pump and entered the bathroom with a bare end (or it's bare end were connected to something metal). That's obviously a silly example/analogy, but it illustrates the problem that the pipe can just be considered as a pipe (which could be an extraneous-c-p) or as an 'electrical extension' of the exposed-c-p of the boiler/pump/whatever!
Kind Regards, John