Tado V3 upgrade

Joined
17 Jan 2014
Messages
27
Reaction score
0
Location
Lancashire
Country
United Kingdom
I was going to replace my current Honeywell BR91 with a Tao v3. The picture is my current working with a live loop to connection A. Can anyone confirm if I’m correct in saying the wiring to the Tado v3 would be the looped wire from L that goes to A would now go to CH COM and B to CH NO?

Many thanks



IMG_7019.jpeg
 
1773532787540.png
A and B replaced with Com and NO, N and L same with both, but there are different versions of Tado. The main reason to swap is often to use the OpenTherm so what boiler and system you have can change how wired.
 
Can anyone confirm if I’m correct in saying the wiring to the Tado v3 would be the looped wire from L that goes to A would now go to CH COM and B to CH NO?
Yes this is correct. If you have opentherm capability on your boiler then it would be better using that, if not go ahead with what you want.
 