Think
In addition to the questions you have already been asked, is this a new occurrence, or has this shower been blowing fuses ever since it was installed?The Heatstore Aqua-Plus blowing 30 amp fuse in consumer unit. Think it is 8.5
please find out for sure. this is important.
Also please show us photo of your consumer unit, and of the thing that is tripping. 30A suggests it is rather old.
How soon after you turn it on does it trip?
True, but if one can find the relevant small print, one discovers that the power consumption of these things are nearly always quoted at 240V, in which case the current drawn by a "8.5 kW" shower at 230V would be roughly ..If your shower is indeed 8.5 KW : 8500W/230V = 36.96A .
AboutIn addition to the questions you have already been asked, is this a new occurrence, or has this shower been blowing fuses ever since it was installed?
Kind Regards, John
It is the older unit"Consumer unit" is the thing that some people used to call a "fusebox"
https://www.screwfix.com/c/electrical-lighting/domestic-consumer-units/cat7230028
Photo of yours please, and of the thing inside it that trips or blows.
NO, a higher rated fuse is NOT OK.Would a 40 or 45 A fuse be okay.
is this a new occurrence, or has this shower been blowing fuses ever since it was installed?
May have to get an electrician out
James