Missed those pics somehow.
The metering is only 100amp max, so this limits the capacity straightaway.
A 63amp TP outlet could be fed from the MCCB panel board with relative ease, and if you do have several gatherings that would utilise this outlet, then it seems appropriate.
It's a TN-S supply, so exporting the earth and using it outside is not an issue.